SECTION 3 - MAINTENANCE OF BATTERY MODULES

2.3.1 Inspection

Liberty 1000 Series Front access modules are sealed VRLA valve-regulat-
ed lead acid batteries and never require the addition of water.

WARNING: Never remove the vents as this will degrade the
battery seal and will void the warranty.

2.3.2 Cleaning Modules

Use only a damp cloth to clean modules. Do not use any cleaning
agents, because they could damage the battery cases.

WARNING: Do not clean modules with a dry cloth since this
could develop a static charge on the plastic containers resulting
in a potential spark.

2.3.3 Cell voltage variation

It is expected that module voltages will vary throughout the normal life
of the battery. An acceptable variation of +/- 0.05 volts from the nom-
inal cell float voltage is satisfactory. As an example a 12 volt module
floating at 2.26 volts per cell or 13.56 volts for the module may vary
from 13.26 to 13.86 volts measured at 77°F (25°C) and be accept-
able.

2.3.4 Effects of temperature

A lead-acid battery is an electro chemical device. Heat accelerates
chemical activity; cold slows it down. Normal battery operating tem-
perature is 77°F (25°C). Higher than normal temperatures have the
following effects on a lead-acid battery:
• Increases capacity
• Shortens life

17

LIBERTY SERIES 1000 FAM AND FA BATTERY

WARRANTY INFORMATION

Warranty period

Maximum annual

average temperature

2 Years full

8 Years pro-rata

77°F (25°C)

1 Year full

4 Years pro-rata

92°F (33.3°C)

1

2

Year full

2 Years pro-rata

107°F (43.3°C)

3 Months full

1 Year pro-rata

122°F (48.8°C)

TABLE 4