FV/Time
Models
1 hr.
3 hr.
5 hr.
8 hr.
10 hr.
20 hr.
FAM 12-100
66.3
28.1
18.5
12.4
10.2
5.5
1.75
FA 12-125
86.3
37.1
24
15.8
12.9
6.8
FAM 12-150
99.9
43
28.1
18.8
15.4
8.2
FAM 12-100
64.7
27.6
18.2
12.3
10.1
5.4
1.80
FA 12-125
83.2
35.8
23.2
15.4
12.6
6.6
FAM 12-150
96.2
42.4
27.8
18.6
15.3
8.1
FAM 12-100
1 hr
3 hr
5 hr
8 hr
10 hr
20 hr
1.84
FA 12-125
78.7
34
22.2
14.7
12.1
6.4
FAM 12-150
92.4
41.7
27.5
18.4
15.1
8
FAM 12-100
57.6
25.3
16.7
11.3
9.3
5
1.88
FA 12-125
72.8
31.6
20.7
13.8
11.3
6
FAM 12-150
92
41.2
27.3
18.3
15
8
FAM 12-100
55.1
24.3
16.1
10.9
9
4.8
1.90
FA 12-125
69.1
30.1
19.7
13.2
10.8
5.8
FAM 12-150
85.3
40.4
27
18.2
14.9
7.9
Ratings in Amperes at 77°F (25°C)