7.0 Spare Parts List
It is recommended that the following spare parts be stored at the installation site for routine maintenance purposes. The quantities required will
depend on the size of the system. Consult with your AAF representative to determine actual quantities required. Minimum recommended
quantities are provided in the table below.
AAF Part Number
Description
Recommended Spares
Refer to the original customer purchase
SAAF cassette gas-phase chemical filters
One full replacement set of each type
order and the AAF submittal drawing.
included in the system.
Refer to the original customer purchase
Particulate filters
One full replacement set of each type
order and the AAF submittal drawing
included in the system.
2500932
Extruded plastic strips which provide
20% of the number supplied
low friction cassette bearing surface
with the equipment
2500924
Hollow core track gasket
One full replacement set or a roll of 50 feet
2500981
Access door perimeter gasket
One full replacement set or a roll of 50 feet
2500999
Access door side seal gasket
One full replacement set
To order replacement parts call: 1-800-477-1214.
8.0 Equipment Characteristics, Dimensions, Operating
Weights, and Shipping Weights
See the AAF submittal drawing supplied on the specific order.
9.0 Technical Guidelines
9.1 Fan selection and sizing: The following guidelines are provided
for the following purposes:
– To assist the user in selecting a fan to operate with the AAF filter
system.
– To inform the user of the criteria used by AAF to select an integral
fan that is provided with an AAF Side Access Housings (SAH).
19
6.2.2 Provide higher efficiency filters on the downstream side (air
leaving side) of the system.
6.3 Odors and Smells:
6.3.1 Check the performance of the gas-phase chemical filters. If
the filters are no longer effective replace them.
6.3.2 Check for missing or damaged filters and system leaks.
Replace filters and reseal as necessary.
9.1.1 Determination of Fan Selection Pressure Drop: The
following concerns initial and final filter pressure drop and the use
of pressure drop for fan selection. AAF’s standard product literature
indicates the start-up, being the clean filter or initial, and the
recommended final, or dirty filter, pressure drops for all filters at a
particular airflow velocity. If the airflow velocity in the actual
installation differs from that referenced in the literature then the
start-up (initial) pressure drop will also differ. For instance, an AAF
PerfectPleat or M-Pak filter is typically rated at 500 FPM velocity,
however, when used with a type HD cassette the airflow velocity
will normally be 250 FPM so the initial pressure drop will be lower.
Similarly, the final pressure drop referenced in the literature is a
“recommended” value only and the filter may be changed out at a
lower pressure drop, if required.