Connect Tube to Low Pressure
Gauge Connection
Connect Tube to High
Pressure Gauge Connection
Static Pressure +2 Inches
Water Gauge *
Filter Bank
Figure 6
*Pressures Shown are for
Illustrative Purposes Only
Static Pressure +1.1 Inches
Water Gauge *
Pressure
Tap (Typ.)
Pressure Gauge
CAUTION: All electrical work must be carried out in accordance
with all appropriate governing electrical codes and standards.
! WARNING: All electrical work has the potential to cause shock,
injury, and even death. Disconnect all power whenever working on
the system. Only qualified electrical personnel should work on the
system at any time.
3.12.1 Provision of an appropriate power supply as specified in the
submittal information.
CAUTION: Use of the incorrect line voltage may result in
irreparable damage to electrical components.
Connect Tube to Low Pressure
Gauge Connection
Connect Tube to High
Pressure Gauge Connection
Static Pressure -2 Inches
Water Gauge *
Airflow
Airflow
Filter Bank
Figure 5
*Pressures Shown are for
Illustrative Purposes Only
*Static Pressure -2.9 Inches
Water Gauge*
Pressure
Tap (Typ.)
Pressure Gauge
Top-mounted gauges may ship separately to prevent the possibility of
shipping damage to the gauge enclosure and gauges. In this case some
simple installation will be required. The gauge(s) will ship installed in an
enclosure which will be screwed to the top of the SAH. Pressure taps will
be supplied on the housing on each side of the filter. These will be
required to be connected to the gauge, using
1
⁄
4
" diameter clear plastic
tubing, as shown in Figures 5 and 6. When the gauge option is ordered the
tubing will be supplied by AAF with the gauge and gauge enclosure. Refer
also to the specific installation instructions supplied with the gauge(s).
If pressure gauge(s) have not been included in the customer’s purchase
order discuss the pressure gauge options with your AAF representative.
3.12 Fans: Sometimes the SAH may be supplied with an internally
mounted fan. See the AAF submittal drawing and wiring diagram for
information and details. In order for the fan to be operated some or all
of the following installation steps may be required:
Fan on
Suction Side
Fan on
Pressure Side
Draw Through System