beautypg.com

3 | areas of application, R407c, R134a – GEA Bock FK50 User Manual

Page 9: D gb f i tr cn

background image

9

09704-09.2013-DGbFIT

rCn

D
GB
F
I
TR
CN

3| Areas of application

Design for other ranges on request

Max. permissible

operating pressure (g) high-

pressure side (HP): 28 bar

Max. permissible

operating pressure (g) high-

pressure side (HP): 28 bar

Unrestricted
application range

Unrestricted
application range

Reduced suction
gas temperature

Reduced suction
gas temperature

Evaporation temperature (°C)

Evaporation temperature (°C)

Condensing temperature (°C)

Condensing temperature (°C)

Suction gas superheat (K)

Suction gas superheat (K)

Suction gas temperature (°C)

Suction gas temperature (°C)

Fig. 4

Fig. 5

20

30

50

70

80

-20

-10

10

0

20

30

t (°C)

o

t (°C)

c

82

-30

40

60

90

t + 25 °C

oh

<

?

t

oh

20 K

R134a

20

30

50

-20

-10

10

0

20

t (°C)

o

t (°C)

c

61

-30

40

60

-25

<

?

t

oh

20 K

t + 25 °C

oh

R407C

3.4.1 Limits of application R134a (N and K versions)

3.4 N and K versions
Models available:

• FKX50/460 N

• FKX50/555 N

• FKX50/660 N

• FKX50/775 N

• FKX50/460 K

• FKX50/555 K

• FKX50/660 K

• FKX50/775 K

• FKX50/830 N

• FKX50/980 N

• FKX50/830 K

• FKX50/980 K

Permissible rotation speeds:
N Design: 500 – 3000 rpm

(max rotation speed 3500 rpm)

K Design: 500 – 3500 rpm

3.4.2 Limits of application R407C (N and K versions)

Permissible rotation speeds:
N Design: 500 – 2600 rpm
K Design: 500 – 3500 rpm