Step 2 — Outdoor Coil, Indoor Coil, and

Condensate Drain Pan

Inspect the condenser coil, evaporator coil, and condensate drain

pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean

the coils either before or after each cooling season. Remove all

obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush

attachment. Be careful not to bend the fins. If coated with oil or

grease, clean the coils with a mild detergent--and--water solution.
Rinse coils with clear water, using a garden hose. Be careful not to

splash water on motors, insulation, wiring, or air filter(s). For best
results, spray condenser coil fins from inside to outside the unit. On

units with an outer and inner condenser coil, be sure to clean

between the coils. Be sure to flush all dirt and debris from the unit
base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all

foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring, or

air filter(s). If the drain tube is restricted, clear it with a plumbers

snake or similar probe device.

Step 3 — Outdoor Fan

Keep the condenser fan free from all obstructions to ensure proper

cooling operation. Never place articles on top of the unit. Damage
to unit may result.

1. Remove 6 screws holding outdoor grille and motor to top

cover.

2. Turn motor/grille assembly upside down on top cover to

expose fan blade.

3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off

motor shaft.

5. When replacing fan blade, position blade back to same posi-

tion as before.

6. Ensure that setscrew engages the flat area on the motor shaft

when tightening.

7. Replace grille.

Step 4 — Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be

sure to turn off the electrical power to the unit.
Remove access panels (see Fig 22) to locate all the electrical

controls and wiring. Check all electrical connections for tightness.
Tighten all screw connections. If any discolored or burned

connections are noticed, disassemble the connection, clean all the

parts, restrip the wire end and reassemble the connection properly
and securely.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling

cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check

each

electrical

component

with

the

proper

electrical

instrumentation. Refer to the unit wiring label when making these
checkouts.

Step 5 — Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil
accumulation annually. Detecting oil generally indicates a

refrigerant leak.
If oil is detected or if low performance is suspected, leak--test all
refrigerant tubing using an electronic leak detector, or liquid--soap

solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.

If no refrigerant leaks are found and low performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.

Step 6 — Indoor Airflow

The heating and/or cooling airflow does not require checking

unless improper performance is suspected. If a problem exists, be
sure that all supply--air and return--air grilles are open and free

from obstructions, and that the air filter is clean. When necessary,
refer to Indoor Airflow and Airflow Adjustments section to check

the system airflow.

Step 7 — Metering Devices--TXV & Piston

This unit uses 2 types of metering devices. The outdoor metering
device is a fixed orifice and is contained in the brass hex--body in

each liquid line feeding the outdoor coils. The indoor metering
device is a TXV type device.