beautypg.com

Radiance direct vent/natural vent gas heater, Vent termination clearances, Vertical termination - direct vent only – Vermont Casting 3225 User Manual

Page 7: Important direct vent only

background image

8

8

Radiance Direct Vent/Natural Vent Gas Heater

20004188

Vent Termination Clearances

When planning the installation, consider the location
of the vent terminal and clearances. Some of the most
common clearances to keep in mind are shown in Figure 9.
Important: All vent clearances must be maintained.
Check your vent termination clearances against
Figures 9 through 11.
The vent should be placed so that people cannot be
burned by accidentally touching the vent surfaces when
the stove is operating.
The vent termination should be located where it cannot
be damaged by such things as automobile doors, lawn
mowers or snowblowers and it should be located away
from areas where it could become blocked by snow,
etc.
Some considerations are:

Obstructions or impediments to venting.

Nearby combustible materials that could come into

contact with combustion exhaust gases.

Other nearby openings {within 12” (305 mm)}

through which exhaust gas could reenter the build-
ing.

All vegetation within 3’ (76 mm) that may interfere

with the draft.

Other factors that influence where the installation will
be sited include the location of outside walls, where
additional heat may be desired in the home, where the
family members gather most regularly, and perhaps
most importantly, the distance limitations of the venting
system.

Vertical Termination - Direct Vent ONLY

A vertical vent system must terminate no less than 8’
(2.44m) and no more than 40’ (12m) above the appli-
ance flue collar. A 2¹⁄₄" restrictor plate (supplied) must
be used, where specified, in all vertically terminated
vent systems. (Refer to Figure 8) NOTE: The restrictor
plate supplied with the vertical termination should
be discarded. Install restrictor plate supplied with
stove directly at stove outlet.
A vertically terminated
vent system must also conform to the following criteria:

No more than three 90° elbows may be used.

Two 45° elbows may be substituted for one 90˚

elbow. No more than six 45° elbows may be used.

Vent must rise a minimum of 2 feet before offset is

used.

Termination height must conform to roof clearance

as specified in Figure 9.

��
��
��
��
��
��
��
��
��
��




���
���



��

� �

�� �� �� �� �� �� �� �� �� ��

Vertical Run (in feet)

(Measure from the appliance flue collar to the top of the vent

pipe.)

Horizontal Run (in feet)

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

ST132a

FDV28

Vertical

vent run

12/3/99 djt

area

modified

1/11/00 djt

ST132a

Fig. 8 Vertical vent termination window.

All Vertical Termi-
nations in this area
Require use of
the 2¹⁄₄” Restrictor
Plate*

Vertical terminations

must be within this area

No offset may be used

within this area

Unacceptable

Venting Configuration

No Restrictor Plate

IMPORTANT

Direct Vent Only

• The horizontal termination must not be recessed

into the exterior wall or siding.

• Horizontal vent runs must be level toward the

vent termination.

• Clearances around the vent termination must be

maintained.

For installations using Simpson DuraVent pipe,
parallel installations with minimum wall clearance
have restricted access for connecting the Hori-
zontal Vent Cap straps to the vent pipe. See the
maker’s instructions for recommended installa-
tion procedures.

*The Restictor Plate is used on Direct Vent
installations only.

This manual is related to the following products: