Installation requirements – Vermont Casting 3225 User Manual
Page 4
5
Radiance Direct Vent /Natural Vent Gas Heater
20004188
Installation Requirements
The installation must conform with local codes or, in
the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEP-
TION: Do not derate this appliance for altitude. Main-
tain the manifold pressure at 3.5” w.c. for Natural Gas,
and 10” w.c. for Propane).
In Canada, installation must be in accordance with the
current CSA B-149.1 Installation Codes and/or local
codes.
The installation should be done by a qualified ser-
vice person who is familiar with the building codes
and installation techniques appropriate for your
area to accomplish a safe and effective installation.
Your dealer or your local gas supplier will be able to
refer a qualified service person.
WARNING: Due to high temperatures, the HEATER
should be located out of traffic and away from furni-
ture and draperies.
The surface of the Heater Is hot when it is in use.
Young children should be watched carefully when
they are in the same room when the Heater is in
use, and they should be taught to avoid the hot
surface. Keep any objects that can burn well away
from the Heater, and observe the recommended
clearances that follow.
Locating The Stove
In choosing a location for the stove, consider:
•
The location of outside walls;
•
Where additional heat is needed:
•
Where family members gather most often;
•
The vent system requirements.
NOTE: We do not recommend the use of wallpaper
next to this stove. Over time, radiant heat may cause
the wallpaper to shrink, or may adversely affect the
binders in the wallpaper adhesive.
ST207a
A. Flat on corner wall
B. Room Divider
C. Island
D. Cross Corner
E. Flat on wall
Fig. 2 Possible stove locations.
Direct Vent System Only
A
B
E
C
D
ST207a
Stardance
Stove locations
9/28/00 djt
Clearance Requirements
Minimum Clearances to Combustible Materials
Measure side clearances as shown in Figures 3, 4 and
5 from the outer edge of the cast iron stove top. Mea-
sure rear clearances from the outermost surface of the
steel rear skirt.
The Radiance heater is approved for installation into
an alcove constructed of combustible materials to the
dimensions and clearances shown on the next page.
The same clearances apply in a standard parallel instal-
lation.
WARNING:
• Always maintain required clearances
(air spaces) to nearby combustibles
to prevent fire hazard. Do not fill air
spaces with insulation. All venting components
must maintain a 1” (25mm) clearance to com-
bustible materials. Maintain a 6” (150mm) clear-
ance when using single wall pipe.
• The gas appliance and vent system must be
vented directly to the outside of the building
and never be attached to a chimney serving a
separate solid fuel or gas-burning appliance.
• Refer to the manufacturer’s instructions includ-
ed with the venting system for complete instal-
lation procedures.