AquaSmart Boiler Control Wiring Guide
Table 2 - Functional Replacement (Advanced Wiring Needed)
Note: Available operating limit and/or differential ranges may not be equivalent. Compare settings to the AquaSmart
ranges before replacing.
AquaSmart Cross-Reference Guide - Functional Replacements
Honeywell
L4006A (All)
L4006G 1022
L4006H 1004
L4008A (All)
L4080B,D
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. ● 7600 will require an additional wire (L2) for
operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused. ● Set low limit on 7600 to OFF. ● To use with a millivolt system an
appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit.
L4006E (All)
L4008E (All)
L4080F,G
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Requires the addition of a manual-reset high limit. ● Make sure 7600 outputs do not exceed 7.4A @ 120VAC. ● 7600 outputs
are not rated for 240 VAC. ● 7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are
unused. ● Set low limit on 7600 to OFF. ● To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must
be added to switch the millivolt circuit.
L6006A (All)
L6006C 1018
L6008A 1192
L6008A 1242
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. ● To use with a millivolt system an appropriate
voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. ● Make sure 7600 outputs do not exceed 7.4A @ 120
VAC. 7600 outputs are not rated for 240 VAC. ● 7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC,
and ZR are unused. ● Set low limit on 7600 to OFF.
L8124B 1039
L8148J 1009
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. 7600 outputs
are not rated for 240 VAC.
L7148F (All)
L8148E (All)
Replace with AquaSmart
7600B
Must confi rm that 7600 VA rating is adequate to meet VA requirements of system. ● Make sure 7600 B1 output does not exceed 1.25A @ 24VAC
(30 VA). ● 7600 outputs are not rated for 240 VAC. B2, TW and TR terminals replace TV, T and Z, respectively. ● If damper is used, consult
damper manufacturer’s wiring instructions for using damper without damper plug.
L4081A/B
L6081A/C
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Remove switching relay, if used, from the system when replacing the L4081 or L6081. ● Make sure 7600 outputs do not exceed 7.4A@120VAC.
7600 outputs are not rated for 240 VAC.
Carlin
90200A
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Make sure 7600 outputs do not exceed 7.4A. Set low limit on 7600 to OFF.
90000
(All)
90200E
90200EL
90300B
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Requires the addition of a manual-reset high limit. Make sure 7600 outputs do not exceed 7.4A. ● Set low limit on 7600 to OFF.
90200D
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. Make sure 7600 outputs do not exceed 7.4A.
Set low limit on 7600 to OFF.
White Rodgers
11B06-1
11D18-1
11B18-101
11B30-104
11B02-1
1145-33
11B06-46
11B95-31
11B18-153
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. 7600 will require an additional wire (L2) for
operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused. ● Set low limit on 7600 to OFF.
11D82-1
11D31-1
1131-102
1127-2
11A79-2
1127-9
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. 7600 outputs are not rated for 240 VAC. ●
7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused. ● Set low limit on 7600 to
OFF.
11B27-9
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
Requires the addition of a manual-reset high limit. ● Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240
VAC. 7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused. ● Set low limit on
7600 to OFF.
8J48A-209
Replace with AquaSmart 7600A or 7600B
(Based on System Voltage Requirements)
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt
circuit.