AquaSmart Boiler Control Wiring Guide
Control Programming
- for optimal energy savings
AquaSmart A or B with Honeywell V8043E/8044E zone valves with indirect H/W
wired as priority
1. High Limit: 180
2. High Differential: 10
3. Low Limit: “OFF”
4. Set DHWP to “ZR”
5. Set Circulator on “BOTH”
6. Circulator On-Delay: “OFF”
7. Circulator Off-Delay: “OFF”
8. Set Economizer to “ON”
9. Set Effi ciency “HI”