AquaSmart Cross-Reference Guide - Direct Replacements
Honeywell
L8124A (All)
L8124C (All)
Replace with AquaSmart 7600A
7600 outputs are not rated for 240 VAC.
L7124A (All)
L7124C (All)
L7148A (All)
L7224A (All)
L7224C (All)
L7224U (All)
L7248A (All)
L7248C (All)
Replace with AquaSmart 7600A
The 7600 has no Honeywell EnviraCOM
TM
Communications port. The diagnostic LED lights are replaced by the
7600’s display.
L8148A (All)
Replace with AquaSmart 7600A
7600 outputs are not rated for 240 VAC. B1 terminal on 7600 utilizes a 1/4” quick connect. Set low limit on 7600
to OFF.
L8124E 1016
L8148E 1265
Replace with AquaSmart 7600B
7600 outputs are not rated for 240 VAC. B2, TW and TR terminals replace TV, T and Z, respectively.
L8124M (All)
Replace with AquaSmart 7600A
For replacement with the 7600: Turn low limit off so the circulator is controlled directly by the thermostat and ZC is
constantly powered.
L8151A
Replace with AquaSmart 7600A
7600 outputs are not rated for 240 VAC. Remote mount sensor cable needed (Part No. 52120)
Hydrolevel
3100
Replace with AquaSmart 7600B
Not a suitable replacement if Low Water Cutoff (LWCO) functionality is used.
3150
Replace with AquaSmart 7600A
Not a suitable replacement if Low Water Cutoff (LWCO) functionality is used.
Carlin
90524A
Replace with AquaSmart 7600A
Make sure 7600 outputs do not exceed 7.4A. Available operating limit and differential ranges are not equivalent.
White Rodgers
11C15-11
Replace with AquaSmart 7600A
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
Available operating limit and differential ranges may not be equivalent.
11C30-3
11B54-4
8B48A-217
Replace with AquaSmart 7600A
11C61-12
Replace with AquaSmart 7600A
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
8F48A-351
8B43A-601
Replace with AquaSmart 7600B
Table 1 - Direct Replacements
Functional replacements on next page ►