Beckett AquaSmart Wiring User Manual
Page 13
13
AquaSmart Boiler Control Wiring Guide
Control Programming
- for optimal energy savings
AquaSmart A or B with Honeywell V8043E/V8044E zone valves & main zone circulator
(with or without tankless H/W coil)
1. High Limit: 180
2. High Differential: 10
3. Low Limit: “OFF”
4. Set DHWP to “OFF”
5. Low Limit: 160 (with tankless H/W coil)
6. Low Differential: 10
7. Set Circulator on “TT”
8. Circulator On-Delay: “30 Seconds”
9. Circulator Off-Delay: 4 minutes
10. Set Economizer to “ON”
11. Set Effi ciency “HI”