Programming basic functions, A. temperature high limit, B. temperature low limit – Beckett 7600 AquaSmart Boiler Control User Manual
Page 26: C. temperature high limit differential

26
To ensure smooth appliance operation, the AquaSmart
requires a separation between the High and Low limits
no less than the greater differential plus 5°F. For
example: If the HIGH LIMIT is set to 180°F, the HIGH
DIFF to 20°F, and the LOW DIFF to 10°F, the control will
not allow a LOW LIMIT above 155°F (180°F - 20°F [the
greater of the two differentials] - 5°F = 155°F).
A. Temperature High Limit
1. In any mode or screen other than an OPTION
sub-menu, press the
“HIGH LIMIT”
key.
2. The following screen will be displayed:
HIGH LIMIT: 180F
CHANGE AND ENTER
The temperature displayed is the current setting.
Use the
▲
and
▼
keys to select the desired setting.
Tap the button to increase or decrease the
temperature by 1°, or hold it to increase or
decrease the temperature by 5° at a time. The
control will not allow you to select out-of-range
values.
3. Press the
“ENTER (RESET)”
key.
4. The control will ask you to confirm the setting with
the following screen:
HIGH LIMIT: 160F
ENTER OR CANCEL
Press
“ENTER (RESET)”
if the value is correct, or
“CANCEL (BACK)”
if it is not.
B. Temperature Low Limit
1. In any mode or screen other than an OPTION
sub-menu, press the
“LOW LIMIT”
key.
2. The following screen will be displayed:
LOW LIMIT: 140F
CHANGE AND ENTER
The temperature displayed is the current setting.
Use the
“▲”
and
“▼”
keys to select the desired
setting. Tap the button to increase or decrease the
temperature by 1°, or hold it to increase or
decrease the temperature by 5° at a time. The
control will not allow you to select out-of-range
values. For cold-start operation, turn the low limit
off by pressing the down arrow key repeatedly until
OFF is displayed.
IMPORTANT: To prevent flue gas condensation
and reduce fatigue caused by thermal cycling on
conventional (non-condensing) boilers, the LOW
LIMIT set point should be 150° F or above.
NOTE: Appliance manufacturer’s temperature
requirements supersede this recommendation.
3. Press the
“ENTER (RESET)”
key.
4. The control will ask you to confirm the setting with
the following screen:
LOW LIMIT: 150F
ENTER OR CANCEL
Press
“ENTER (RESET)”
if the value is correct, or
“CANCEL (BACK)”
if it is not.
C. Temperature High Limit Differential
1. In any mode or screen other than an OPTION
sub-menu, press the
“HIGH DIFF”
key.
2. The following screen will be displayed:
HIGH DIFF: 10F
CHANGE AND ENTER
The temperature displayed is the current setting.
Use the
“▲”
and
“▼”
keys to select the desired
setting. Tap the button to increase or decrease the
temperature by 1°, or hold it to increase or
decrease the temperature by 5° at a time. The
control will not allow you to select out-of-range
values.
Programming Basic Functions
Figure 18 - AquaSmart Keypad
Electrical Shock Hazard.
Can cause severe injury, death, or
equipment damage.
Live line voltage wires and connections will be exposed
while programming the AquaSmart. Take care to touch
only the AquaSmart keypad while programming the control.
Fire, Explosion, and
Burn Hazards.
Can cause severe injury, death, or
equipment damage.
Do not set the operating limits of the control outside of
those listed by the appliance manufacturer.