beautypg.com

Reset button operation – Beckett SM User Manual

Page 14

background image

14

Figure 9a. – Interrupted ignition, valve-on delay only
(no motor-off delay)

Figure 9b. – Interrupted ignition, valve-on delay and
motor-off delay

SAFETY AND

OPERATING

LIMITS

LIMIT

L1

L2 (VLV)

VALVE

L2

MOTOR

L2 (MTR)

L2 (IGN)

IGNITER

CAD
CELL

MOTOR

IGNITER

W

R

80

70

60

50

50

70

80

60

OIL VALVE

CAD CELL

THERMOSTAT

TR

TW

TR-TW

JUMPER

TR-TW TERMINALS

LOCATED ON OPPOSITE

SIDE OF CONTROL

L1
L2

SAFETY AND

OPERATING

LIMITS

LIMIT

L1

L2 (VLV)

VALVE

L2

MOTOR

L2 (MTR)

L2 (IGN)

IGNITER

CAD
CELL

MOTOR

IGNITER

W

R

80

70

60

50

50

70

80

60

OIL VALVE

CAD CELL

THERMOSTAT

TR

TW

TR-TW

JUMPER

TR-TW TERMINALS

LOCATED ON OPPOSITE

SIDE OF CONTROL

L1
L2

LIMIT

L1 - LIMIT
JUMPER

Table 2 - Reset Button Operation

If the burner is in the

below state:

Pushing the reset button will:

Button Click

(press < 1 second)

Button Hold

(press > 1 second)

Button Hold

(press 15+ seconds)

Lockout

Reset from Soft Lockout

Reset from Restricted (Hard)
Lockout

Valve-on Delay, Trial for
Ignition, Ignition Carryover

Go to Pump Prime (see
“Priming the Pump” above)

Disable the Burner:
Any time the burner is running,
press and hold the reset button
to disable the burner. The
burner will remain off as long
as the button is held.

Enables Pump Priming:
After the reset button has been
held for 15 seconds, the button
can then be clicked during the
next ignition sequence to enter
Pump Prime mode.

Run (igniter is shut off)

No action

Motor-Off Delay,
Standby

No action

Pump Prime

No action

Exit Pump Prime mode and return to Standby

Table 3 - Status Lights

Light Color

On Continuously

Flashing

Red

Restricted (Hard) Lockout

Soft Lockout

Green

Flame Sensed during normal operation (Could
be stray light during standby)

Recycle

Yellow

Control is in Pump Prime mode or
Reset button currently held for 15+ seconds.

N/A

Reset Button Operation

Table 2 explains what action the control will take when the reset button is pressed for different lengths of time during
the various burner operating states.

Section: Burner Controls