beautypg.com

Kidde i12080A User Manual

Page 3

background image

FIGURE 1

FIGURE 2

FIGURE 3

• Locate at least one alarm on every floor level.

• Locate an alarm in every sleeping room.

• Locate an alarm in every room where electrical appliances are operated (i.e.

portable heaters or humidifiers).

• Locate an alarm in every room where someone sleeps with the door closed.

The closed door may prevent an alarm not located in that room from waking
the sleeper.

• Smoke, heat, and combustion products rise to the ceiling and spread horizon-

tally. Mounting the smoke alarm on the ceiling in the center of the room
places it closest to all points in the room. Ceiling mounting is preferred in
ordinary residential construction.

• For mobile home installation, select locations carefully to avoid thermal

barriers that may form at the ceiling. For more details, see MOBILE HOME
INSTALLATION.

• When mounting an alarm on the ceiling, locate it at a minimum of 4” (10 cm)

from the side wall (see figure 1).

• When mounting the alarm on the wall, use an inside wall with the top edge

of the alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm)
below the ceiling (see figure 1).

• Put smoke alarms at both ends of a bedroom hallway or large room if the

hallway or room is more than 30 ft (9.1 m) long.

1220-7205-00(820-1183D-EN).qxd:_ 2010.9.3 7:04 PM Page 3

This manual is related to the following products: