High Altitude Installations
The default setting for the water is 0-2,000 ft (0-610 m) with dip switch numbers 2 and 3 in the OFF
position. If this water heater is installed at a higher altitude, it is necessary to modify the dip switch
settings according to Table 5.
Table 5.
Dip Switch Settings for High Altitude Installations.
0-2000 ft
(0-610 m)
2001-5200 ft
(610-1585 m)
5201-7700 ft
(1585-2347 m)
7701-10200 ft
(2347-3109 m)
Switch No. 2
OFF
OFF
ON
ON
Switch No. 3
OFF
ON
OFF
ON
Switch N o.
F
O
F
8
5
7
6
4
3
ON
1
2
Switch N o.
F
O
F
8
5
7
6
4
3
ON
1
2
Switch N o.
F
O
F
8
5
7
6
4
3
ON
1
2
Switch N o.
F
O
F
8
5
7
6
4
3
ON
1
2
This manual is related to the following products:
See also other documents in the category Bradford White Water boiler:
- EFR-1-60T1206EN (76 pages)
- S-2-TW65T6FBN (11 pages)
- D-38T-155-3X (1 page)
- PDX1-40S6FSX (13 pages)
- EF-100T-300-3X (92 pages)
- M-4-30T6FBN (28 pages)
- M-4-30T6FBN (32 pages)
- M-4-30T6FBN (28 pages)
- M-4-30T6FBN (40 pages)
- M-I-30T6FBN (30 pages)
- M-2-XR75S6BN (1 page)
- PDX2-75T6FBN (44 pages)
- U-1-75S6RN (1 page)
- U4-40T6FRN (12 pages)
- U1-50L6FRN (12 pages)
- U1-50L6FRN (28 pages)
- M-2-TW-50T6FSX (36 pages)
- M-4-XRTW50T6FSX (40 pages)
- TW4-50S-67FB-3X (40 pages)
- TW4-50S-67FB-3N (44 pages)
- M-2-TW-50T6FSX (44 pages)
- M-2-TW-50T6FSX (36 pages)
- C-SW2-TW75T10BN (8 pages)
- GX-2-25S6SX (28 pages)
- C-SW2-75T10BN (28 pages)
- S-2-65T6FBN (28 pages)
- PE-4-403S6FBN (32 pages)
- PE-4-403S6FBN (16 pages)
- PE-4-40T6FBN (68 pages)
- GX-2-25S6SX (28 pages)
- M-I-100T6SX (28 pages)
- C-SW2-75T10BN (4 pages)
- C-SW2-75T10BN (25 pages)
- HE-4-40S6FBN (40 pages)
- HE-4-40S6FBN (16 pages)
- UDS1-50S6FRN (32 pages)
- DH-50T-50FB-3X (40 pages)
- DS1-40S6FBN (32 pages)
- U-1-75S6RN (28 pages)
- U-75T-80R-3N (8 pages)
- D-4-403S6FBN (36 pages)
- D-4-403S6FBN (40 pages)
- GX-2-TW-25S6SX (40 pages)
- U-1-TW-40S6FRN (48 pages)
- M-2-TW-50T6FSX (44 pages)