Eco-magnum – Bradford White U-100T-88R-3N User Manual

Page 6

background image

Page 6

LED Status

Control Status

Probable Cause

Service Procedure

Three flashes

and three

second

pause.

Insufficient water

heating. System will

reset.

1. Thermowell
sensor and chamber
temperature sensor
out of calibration.
2. Possible short.

1&2. Replace gas
control, see page 15.

Four flashes

and three

second

pause.

Excessive tank

temperature. System

must be reset.

1. Thermowell
sensor out of
calibration.
2. Faulty gas valve.

1. See page 14.
2. Replace gas control,
see page 15.

Five flashes

and three

second

pause.

Thermostat well fault.

1. Damage to the
thermowell wire.
2. Thermowell
sensor resistance
out of range.

1&2. Replace gas
control, see page 15.

Seven flashes

and three

second

pause.

Gas valve electronic

fault detected.

1. Control needs to
be reset
2. Control is wet or
physically damaged

1.Turn gas control knob
to "OFF" position and
then follow lighting
instructions.
2. Replace gas control,
see page 15.

Eight flashes

and three

second pause

False pilot flame

present.

Pilot valve stuck in
open position.

Replace gas control, see
page 15.

Gas Control Troubleshooting

ECO-MAGNUM

75/100-Gallon Atmospheric

6