Page 5

LED Status

Control Status

Probable Cause

Service Procedure

None (LED not on

or flashing)

Gas valve is not

powered.

1. Pilot flame is not
present. Light pilot.

If the pilot will not stay lit
replace thermopile, see
page 11. If problem
persists replace gas
valve, see page 15.

One flash and

three second

pause.

1. If set point knob is in

"PILOT" position then

pilot flame is detected.

Turn set point knob to

desired setting

2. If set point knob is at
desired setting the gas

valve is waiting for a

call for heat (no faults).

1. Gas valve is
powered and waiting
for the set point knob to
be turned to a water
temperature setting.
2. Temperature
demand is satisfied.

Normal operation. Adjust
thermostat to desired
temperature level.

LED strobe (two

quick flashes) and

three second

pause.

Thermostat calling for

heat (no faults).

Tank temperature
below setpoint of
thermostat.

Normal operation.

LED on

continuously.

Set point knob has

been recently turned to

the "OFF" position.

Wait until LED goes out

before attempting to

relight

Set point knob was
turned to "OFF"
position.

LED will go out and the
control will function
normally when the pilot is
lit.

Two flashes and

three second

pause.

Weak pilot flame

detected. System will

reset when pilot flame

is sufficient.

1. Thermopile failure
2. Unstable pilot.
3. Pilot tube block or
restricted.
4. Resettable thermal
switch has opened.

1. See page 10.
2&3. See page 12.
4. See page 18.

Observe green LED indicator on
gas control. Error flash codes are
displayed with a three second
pause before repeating. Check
and repair the system as noted in
the troubleshooting table below.

Gas Control Troubleshooting

Green LED

Indicator

ECO-MAGNUM

75/100-Gallon Atmospheric

5