Burner maintenance – Bradford White PE-2-XR504T6FSX User Manual
Page 17
Page 17
Note: The Burner Maintenance section replaces pages 31-33 in the Defender
Atmospheric service manual, p/n 238-44943-00.
Burner Inspection
At periodic intervals (every 6 months), a visual inspection should be made of the pilot
and main burner for proper operation and to assure no debris is accumulating. The
pilot flame should be stable. Some causes for an unstable pilot flame are:
a) Gas pressure is out of specification.
b) Pilot flame not fully engulfing spark/flame sensor.
The main burner should light smoothly from the pilot and burn with a blue flame with a
minimum of yellow tips.
Steel burner models self adjust air to gas ratio mixture and do not have an adjustable
air shutter. The main burner must be free from any debris accumulation that may
effect burner operation (See Burner Cleaning Procedure on page 17).
Burner Cleaning Procedure
Step 1.
Move the gas control power switch to the “OFF”
position.
Step 2.
Unplug the water heater and Accessory Module from the
wall outlet.
Step 3.
Turn off the gas supply to the water heater.
Step 4.
Remove the outer door.
Burner Maintenance
Gas control power
switch
Water heater power cord and
Accessory Module transformer
Outer door
17