Gas Conversion Instructions continued-
7. Replace the burner assembly and reconnect all fittings and check for leaks.
Refer to “Gas Connections”.
8.
Close and/or replace inner and outer doors.
Note: For closed combustion product, make sure screws are tight and seal
is made around gas supply tube to burner.
9. To light pilot, follow the lighting instructions provided on the water heater
and in this installation and operation instruction manual.
10. Remove “equipped for” card from cloth bag and attach to gas piping as
close to gas control as possible. Remove and discard tag attached to water
inlet fitting of the water heater.
To convert from natural gas to LP gas
(For control shown in Figure 7 only)
1. Follow the instructions above except remove cap from gas regulator, and
depress and rotate plunger counterclockwise
2. Remove main burner orifice and pilot assembly and replace with “RED”
color coded L.P. orifice and pilot assembly provided in cloth bag attached to
the water heater.
3. Replace “equipped for” tag with tag supplied in cloth bag for gas being used.
To convert from L.P. gas to natural gas
(For control shown in Figure 8 only)
1. Rotate and partially depress gas control knob clockwise
to “OFF”
position.
2. Remove the plastic cover from the regulator cap, revealing threads. The
letters “LP” and “NAT” with arrows will be visible.
3. Using an open-ended wrench, turn the regulator cap counter clockwise
, until it comes off. Turn the regulator cap around so the arrow next to
“NAT” is facing toward the gas valve. Reinstall the regulator cap by turning
it clockwise
, until tight.