Honeywell Gas Control Troubleshooting Chart

LED Status

Control Status

Probable Cause

None (LED not on

or flashing

Gas Control is operating normally.
Pilot flame may not be present.
Check for pilot flame through sight
glass and light if necessary.

If set point knob is in “PILOT”
position then pilot flame is
detected. Turn set point knob to
desired setting.

One flash and

three second

pause

LED on

continuously

(Solid)

Set point knob has been recently
turned to the “OFF” position. Wait
until LED goes out before
attempting to relight

Two flashes and

three second

pause

Weak pilot signal detected. System
will reset when pilot flame is
sufficient.

1. Gas Control is functioning
normally.
2. Gas Control is not powered. Light
pilot.
3. Thermopile failure.

Gas Control is powered and waiting
for the set point knob to be turned to
a water temperature setting.

Set point knob was turned to “OFF”
position.

1. Thermopile failure
2. Unstable pilot
3. Pilot tube block or restricted.
4. Resettable thermal switch has
opened

Service

Procedure

If the pilot will not stay
lit replace pilot
assembly. If problem
persists replace Gas
Control.

Normal operation.
Adjust thermostat to
desired temperature
setting.

LED will go out and the
control will function
normally when the pilot
is lit.

1. See service

procedure RG-II

2. See service

procedure RG-III

3. See service

procedure RG-III

4. See service

procedure RG-VIII

Flammable Vapor Ignition Resistant Water Heaters

Green LED Indicator

Observe green LED indicator on
Gas Control. Error flash codes are
displayed with a three second pause
before repeating. Check and repair
the system as noted in the
troubleshooting table below.

Three flashes and

three second

pause

Insufficient water heating. System
will reset.

1. Temperature sensor out of

calibration

1. See service

procedure RG-VI

Four flashes and

three second

pause

Excessive tank temperature.
System must be reset.

1. Temperature sensor out of

calibration

2. Faulty Gas Control

1. See service

procedure RG-VI

2. See service

procedure RG-VI