B&C Technologies DI-475 Industrial User Manual
Page 32

F. DRIVE SYSTEM SOFT START
The DA-475 dryer is equipped with either a Series
154-A11NB
OR 21B
soft start control.
ALL
soft start controls are factory preset. Re-adjustment should not be necessary.
1. Series 154-A11NB OR 21B Drive System Soft Start
Wiring
The
Series 154-A11NB
OR 21B is a motor controller and is used with an electromechanical
motor starter. The controller is wired after the motor starter as shown in the
illustration
below.
The output side of the motor starter should be wired to the line terminals on the controller,
(L1,L2,L3). The load terminals on the controller, (T1,T2,T3) then
Should be
wired to the
motor.
When the motor starter is turned on, 3-phase (3 ) power will be applied to the input to the
controller. The controller will then ramp up the voltage to the motor. The duration of the ramp
will
depend on the setting of the soft start adjustment. When the motor starter is turned off, the
controller will reset and will be ready for the starter to be turned on again.
NOTE:
THE STARTER MUST REMAIN OFF FOR A MINIMUM OF
½ SECOND TO ALLOW
THE CONTROLLER TO COMPLETELY RESET IF THE STARTER IS TURNED ON
BEFORE THE CONTROLLER RESETS, AN ACCEPTABLE SOFT START MAY BE