Conair EARTHSMART UGH031-0209 User Manual
Page 20

2 - 8
l D e s c r i p t i o n
S p e c i f i c a t i o n s : E a r t h S m a r t
T M
E C M
S e r i e s C h i l l e r s
A
B
C
TPHS039-1208
MODEL
ECM-0.5
ECM-0.75
Performance characteristics
Capacity* tons
0.41
0.70
Compressor Hp {kW}✝
0.5 {0.37}
0.75 {0.56}
Pump Hp {kW}
0.25 {0.19}
0.5 {0.37}
Chilled water flow‡ gpm {lpm}
0.9 {3.4}
1.7 {6.4}
Chilled water pressure‡ psi {bar}
60 {4.1}
60 {4.1}
Reservoir capacity gal {liters}
10 {37.8}
10 {37.8}
Dimensions inches {mm}
A - Height
39.7 {1008}
39.7 {1008}
B - Width
18.7 {475}
18.7 {475}
C - Depth
24.2 {615}
24.2 {615}
Process connections inches {mm}
Process (to and from)
0.5
0.5
Weight lb {kg}
§
Installed
223 {101}
233 {106}
Shipping
170 {77}
180 {82}
Voltages full load amps
**
115V/1 phase/60Hz
14
NA
220V/1 phase/60Hz
NA
11
Refrigerant
R-134A
Refrigerant charge lb {kg}
1.3 {0.6}
1.3 {0.6}
SPECIFICATION NOTES:
*
Ton capacity at 12,000 BTU/ton @ 50°F {10°C} leaving
water temperature @ 115°F {46°C} condensing tempera-
ture. Capacities may be ± 5% as reserved by the
compressor manufacturer. Capacity multipliers are: 50°F
{10°C} - 1.00; 40°F {4.4°C} - 0.80.
✝
The ECM Series Chiller uses a hermetic reciprocating
compressor.
‡
Consult pump curve for exact characteristics relating to
pump performances.
§
Chiller installed weight includes a completely filled
reservoir.
**
No allowance for inrush current. Ground fault interruption
to be supplied by the customer. Full load amps must be
used to size supply conductors. Consult a Conair repre-
sentative for 50 Hz operation.
Specifications can change at any time. Contact your Conair
representative for the most current information.