Normal Operation

An LED (light--emitting diode) indicator is provided on the

integrated gas unit controller (IGC) to monitor operation. The IGC
is located by removing the control access panel (see Fig. 20).

During normal operation, the LED is continuously on (See Table 5
for error codes).

Airflow and Temperature Rise

The heating section for each size unit is designed and approved for

heating operation within the temperature--rise range stamped on the
unit rating plate.
Table 9 shows the approved temperature rise range for each heating
input, and the air delivery cfm at various temperature rises for a

given external static pressure. The heating operation airflow must

produce a temperature rise that falls within the approved range.
Refer to Indoor Airflow and Airflow Adjustments section to adjust

heating airflow when required.

Heating Sequence of Operation

(See Fig. 15--17 and unit wiring label.)
On a call for heating, terminal W of the thermostat is energized,

starting the induced--draft motor. When the pressure switch senses
that the induced--draft motor is moving sufficient combustion air,

the burner sequence begins. This function is performed by the
integrated gas unit controller (IGC). The indoor (evaporator)--fan

motor is energized 45 sec after flame is established. When the

thermostat is satisfied and W is de--energized, the burners stop
firing and the indoor (evaporator) fan motor shuts off after a

45--sec time--off delay. Please note that the IGC has the capability
to automatically reduce the indoor fan motor on delay and increase

the indoor fan motor off delay in the event of high duct static

and/or partially--clogged filter.

Limit Switches

Normally closed limit switch (LS) completes the control circuit.

Should the leaving--air temperature rise above the maximum

allowable temperature, the limit switch opens and the control
circuit “breaks.” Any interruption in the control circuit instantly

closes the gas valve and stops gas flow to the burners. The blower
motor continues to run until LS resets.
When the air temperature at the limit switch drops to the
low--temperature setting of the limit switch, the switch closes and

completes the control circuit. The direct--spark ignition system

cycles and the unit returns to normal heating operation.

Table 5 – LED Indications

STATUS CODE

LED INDICATION

Normal Operation

2

On

No Power or Hardware Failure

Off

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Four Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Pressure Switch Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

Temporary 1 hr auto reset

1

9 Flashes

NOTES:

1.This code indicates an internal processor fault that will reset itself in one

hr. Fault can be caused by stray RF signals in the structure or nearby. This

is a UL requirement.

2. LED indicates acceptable operation. Do not change ignition control

board.

3. When W is energized the burners will remain on for a minimum of 60 sec.

4. If more than one error code exists they will be displayed on the LED in

sequence.

Rollout Switch

The function of the rollout switch is to close the main gas valve in

the event of flame rollout. The switch is located above the main

burners. When the temperature at the rollout switch reaches the
maximum allowable temperature, the control circuit trips, closing

the gas valve and stopping gas flow to the burners. The indoor
(evaporator) fan motor (IFM) and induced draft motor continue to

run until switch is reset. The IGC LED will display FAULT CODE

7.

Step 3 — Start--up Cooling and Make Adjust-

ments

Complete the required procedures given in the Pre--Start--Up

section before starting the unit. Do not jumper any safety devices

when operating the unit. Do not operate the compressor when the
outdoor temperature is below 40°F (4.4°C) (unless accessory

low--ambient kit is installed). Do not rapid--cycle the compressor.
Allow 5 minutes between on cycles to prevent compressor damage.

Checking Cooling Control Operation

Start and check the unit for proper cooling control operation as

follows:

1. Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is
placed in AUTO position.

2. Place SYSTEM switch in COOL position and FAN switch

in AUTO position. Set cooling control below room

temperature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle

shuts down when control setting is satisfied. The evaporator
fan will continue to run for 90 sec.

IMPORTANT: Three--phase, scroll compressors are direction
oriented. Unit must be checked to ensure proper compressor
3--phase power lead orientation. If not corrected within 5 minutes,
the internal protector will shut off the compressor. The 3--phase
power leads to the unit must be reversed to correct rotation. When
turning backwards, the difference between compressor suction and
discharge pressures will be minimal.

Checking and Adjusting Refrigerant Charge

The refrigerant system is fully charged with PuronR (R--410A)
refrigerant and is tested and factory sealed. Allow system to operate

a minimum of 15 minutes before checking or adjusting charge.
NOTE: Adjustment of the refrigerant charge is not required unless
the unit is suspected of not having the proper PuronR (R--410A)
charge.
The charging label and the tables shown refer to system
temperatures and pressures in cooling mode only. A refrigerant

charging label is attached to the inside of the compressor access
panel (see Fig. 20). The chart includes the required liquid line

temperature at given discharge line pressures and outdoor ambient

temperatures.
An accurate thermocouple-- or thermistor--type thermometer, and a

gauge manifold are required when using the subcooling charging
method for evaluating the unit charge. Do not use mercury or small

dial--type thermometers because they are not adequate for this type

of measurement.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
When evaluating the refrigerant charge, an indicated

adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an

abnormal condition exists somewhere in the cooling system,
such as insufficient airflow across either coil or both coils.

!

CAUTION

48E

S

--