Vintage Cellars LECBILD1800 User Manual
Page 23

B I L D W I N E C A B I N E T S
-23-
Alarms
Alarm
Indicators*
The control panel has an audible buzzer and an alarm indicator light (Row 4)
that turns on when an alarm is triggered. In addition, the control panel will
flash the following codes when an alarm is triggered:
Alarm Code
What it means
What to do
P1, P3
Probe Failure
Call CellarPro at 877.726.8496
HA
The temperature inside
the cellar is too warm
(>70°F for more than 1
hour)
Check seals;
Check if door was left open;
Lower the ambient temperatures
HA2
The condenser
temperature is too high
(above 140°F for 2
hours)
Check for appropriate installation, ventilation,
ambient conditions and cooling capacity
Clean the condenser coils and/or replace the air
filter;
Check for obstructions to the intake and/or
exhaust vents;
Check that the condenser fan is operating
LA2
The temperature at the
condenser coils
(outside the cabinet)
has dropped below the
alarm temperature
setting
Lower the alarm temperature setting as follows:
1. Depress the “Set” and “Down” button for
three seconds until the controller displays a
parameter (eg “HY”), then release
2. Depress the “Set” and “Down” button again
for seven seconds until the “PR2” flashes on
the display, followed quickly by a parameter
(eg “HY”), then release
3. Using the “Down” button, scroll until the
display reads “AL2”
4. Depress the “Set” button
5. Use the “Down” button to lower the alarm
temperature setting to 45
6. Depress the “Set” button again
7. After three seconds, the display will return to
the normal screen
* Please note: the temperature alarms (HA, HA2, LA and LA2) are disabled during the first 23
hours of operation after the cooling unit is plugged in and/or turned on.