7

A venting system shall not terminate within .3m (1ft) of the following:
• Above grade level or any surface that may support snow, ice, or debris

CAUTION: The owner of the SS2 must keep the area around the vent terminal free of snow, ice and debris.

TION

INSTALLATION TOOLS REQUIRED

• Nut Runner Set

• Drill w/Bits

• Combination Wrench Set

• Screwdriver Set

• Wire Cutter/Stripper

• Draft Gauge

• Smoke Tester

• CO2 Analyzer

• Reciprocating Saw

SS2 VENT SYSTEM CLEARANCES FROM COMBUSTIBLES & OBSTRUCTIONS

With an inlet flue gas temperature of 650oF (343oC) or below, the SS2 has been Listed for Zero Clearance from combustibles.

NOTE: You must allow a minimum 2 foot distance of unobstructed clearance behind the SS2 Vent System for doing

maintenance. Allow 6” minimum clearance from bottom of vent cabinet to any obstruction for air flow.

If possible, do not terminate the SS2 on a wall that faces the direction of the prevailing winds.
Backdrafts by severe winds can cause oil odors to remain in the structure and/or interrupt
equipment operation.