beautypg.com

Smart Power Systems HR-30 User Manual

Page 40

background image

Smart Power

®

Systems

A. C. MODULAR GENERATOR SYSTEM

Page 39 of 50

Note: The fault “Classes” are defined in the table below:

Class Meaning

Service Warning

Normal maintenance needs to take place.

Alarm

A condition requires the immediate attention of the operator.

Shutdown

A condition causes the immediate shutdown of the generator.

Override

A condition that will cause the generator to be shut down in 30
minutes unless explicitly overridden by the operator.

Table 3

Hydraulic Problems:

1.

Cavitation:

Cavitation is caused by trying to pump more fluid than is available at the
pump
inlet due to system restrictions. Pump cavitation sounds like “marbles”
passing through the pump. Conditions frequently associated with cavitation are the
following:

a. Too many restrictive fittings such as elbows and reducers on the pump inlet

hose.

b. Tight bends or kinks in pump inlet hose and/or tubing.
c. Insufficient tray height above the pump, resulting in low head pressures.
d. Under sized pump inlet hose (minimum pump inlet hose size is 1”).
e. Excessively long inlet hose (may be corrected by using larger hose).
f. Cold hydraulic fluid.

Finding the cause and correcting it should stop cavitation.

Install a 0-25 psig gauge in line between inlet hose fitting and pump inlet port.
Engage PTO. Operate genset with no load for twenty minutes to purge air out of
the system. Observe the pressure reading. The pressure should always be
positive. If the pressure is not positive, system repair/rework is required.



2.

Aeration:

Aeration results from air being drawn into the system through leak paths or a
low fluid condition. Aeration makes a “growling” sound and produces visible
bubbles in the fluid stream and/or reservoir. Conditions frequently associated with
aeration are the following:

a. Air leaks in the pump inlet flow path.
b. Low fluid level allowing air to be drawn into the system.

Verify there are no air bubbles in the fluid by viewing inside the reservoir. If there
are air bubbles, check fluid level, tighten all fittings, and look for cracked fittings or
hose leaks on the pump inlet line. Replace any suspect parts and adjust fluid level.

This manual is related to the following products: