beautypg.com

Operation, Troubleshooting, Maintenance – KMC Controls VCZ-44 Series User Manual

Page 3: Accessories/repair parts, Select specifications

background image

VEZ-41/44 Series, 2-Way/3-Way, NPT, Pneumatic Zone Control Valves

3

Installation Guide

© 2009 KMC Controls, Inc.

056-019-02

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Maintenance

No routine maintenance is required. Each component

is designed for dependable, long-term reliability, and

performance. Careful installation will also ensure

long-term reliability and performance.

Operation

After the mechanical and pneumatic installations

have been completed, cycle the actuator to verify

proper operation.

Accessories/Repair Parts

NOTE: Older MCP-6001/6002 actuators are not

compatible with these valve bodies.

NOTE: The last digit (“D” or “E”) of the valve

model number represents the type of

actuator.

Replacement Actuators

HPO-5114

Replacement actuator dia-

phragm

MCP-6101

“D” actuator, 3–8 psi

MCP-6102

“E” actuator, 8–13 psi

Replacement Valve Bodies

VFZ-4102AM

2-way, 1/2", 1.0 Cv

VFZ-4102BM

2-way, 1/2", 2.5 Cv

VFZ-4102CM

2-way, 1/2", 4.0 Cv

VFZ-4103AM

2-way, 3/4", 4.1 Cv

VFZ-4104AM

2-way, 1", 7.0 Cv

VFZ-4402AM

3-way, 1/2", 1.0 Cv

VFZ-4402BM

3-way, 1/2", 2.5 Cv

VFZ-4402CM

3-way, 1/2", 4.0 Cv

VFZ-4403AM

3-way, 3/4", 4.1 Cv

VFZ-4404AM

3-way, 1", 7.0 Cv

Select Specifications

(See the data sheet for additional specifications.)

General

Mounting Location NEMA 1 (interior only)
Temperature Limits

Medium

34 to 230° F (1 to 110° C)

Ambient

40 to 180° F (4.4 to 82° C)

Shipping

–40 to 180° F (–40 to 82° C)

Actuators

Operating Range

3–8 or 8–13 psi

Max. Air Pressure 30 psi (207 kPa)

Valve Body

Service

Hot or chilled water, up to

50% glycol

Flow Characteristics Linear
Max. Inlet Pressure 125 psig (862 kPa)
Max. Close-Off

(AB-A in 3-way)

Valve

Size

(inches)

Cv

Max. Close-Off Ratings (psi)**

8–13 psi Actuator

3–8 psi Actuator

15 psi*

20 psi*

15 psi*

20 psi*

0.5

1.0

30

125

125

125

0.5

2.5/4.0

13

89

112

125

0.75

4.1

13

89

112

125

1.00

7.0

4.4

53

68

116

*Pressure applied to actuator

**Not to exceed body rating

Troubleshooting

If the actuator does not fit properly on the valve body

during installation or the valve performs improperly

(e.g., never fully closes) after installation, check that

the black plastic attachment support ring has been

removed from the valve body top. See the Mounting

Actuators on Valve Body section.

This manual is related to the following products: