Pre-Installation Tasks
|
23
4.0 Pre-Installation Tasks
Before installing any components, follow the
safety information in the ETS-Lindgren
Product Information Bulletin included with your
shipment.
Prior to installing the Model 4340 Digital Camera System (CCTV), complete
these pre-installation tasks.
If you are installing one of the optional configurations listed under
Optional Configurations and Additional Components on page 10,
additional pre-installation tasks may be required. For a description of
pre-installation tasks for optional configurations, see Install Optional
Components on page 33.
Demonstrate Good Shielding Practices
Certain guidelines must be followed to retain the RF shielding integrity of the
chamber. These good shielding practices consist of the following:
Doors must be periodically cleaned and lubricated.
Screw-retaining items mounted within the enclosure must not
penetrate through both shields of a modular panel system. Screws
must not penetrate the screen system of a Series 60 at all.
Framing screws must never be used to fasten items within the
enclosure.
When a hole is bored for a new penetration, all burrs must be removed
and both the perimeter of the hole and the penetration must be
cleaned with a cleaning agent before installing the new penetration.
Nothing must penetrate the enclosure wall, floor, or ceiling without use
of a proper electromagnetic-designated penetration.