V9.14
Up and Down Buttons
To view the “High Temp” recorded by the
cooling unit, press the “Up” button once.
To view the “Low Temp” recorded by the
cooling unit, press the “Down” button once.
To reset the “High Temp” or “Low Temp”, press
the “Set” button for three seconds while “Hi”
or “Lo” is displayed. “RST” will blink three times
to indicate confirmation.
Set Button
The cooling unit is factory preset with a
Minimum Set Point of 58°F and a Temperature
Differential of 4°F. This means that the cooling
unit will turn on when the display rises above
62°F (58°F + 4°F), and turn off when the
display falls below 58°F. In this example, the
average temperature inside the cellar will be
60°F.
To view the Minimum Set Point, press the “Set”
button for one second.
To change the Minimum Set Point,
Press the “Set” button for three seconds
until °F” blinks
Press “Up” or “Down” button
Press “Set” button to confirm
The “Set” temperature will blink three times to
indicate confirmation
The recommended Minimum Set Point range
is 53 - 60°F. To change the Temperature
Differential, see “Advanced Operation” later
in this chapter.