beautypg.com

CellarPro 1800XT-220V WARRANTY SERVICE, 11402 User Manual

Page 19

background image

18

Alarms

The cooling unit has both an audible notification and a visual alarm indicator (shown
in “red” on the control panel) that are activated when an alarm is triggered. Please
note: the temperature alarms (HA, HA2, LA and LA2) are disabled during the first 23

hours of operation after the cooling unit is plugged in and/or turned on.
The control panel also will flash a code for each alarm, as follows:

Alarm Code

What it means

What to do

P1, P2, P3

Probe Failure

Call CellarPro at 877.726.8496

HA

The temperature inside
the cellar is too warm
(above 21.1°C for more

than 1 hour)

Check seals;
Check if door was left open;
Lower the ambient temperatures

HA2 The

condenser

temperature is too high
(above 60°C for 2

hours)

Check for appropriate installation,
ventilation, ambient conditions and
cooling capacity (Chapter II)
Clean the condenser coils (see

“Maintenance” in Chapter IV);
Check for obstructions to the intake
and/or exhaust vents;
Check that the condenser fan is
operating

LA

The temperature inside
the cellar is too cold
(below 7.2°C)

Raise the ambient temperature;
Raise the “Minimum Set Point”

LA2

The temperature at the
condenser coils

(outside the cabinet)
has dropped below the
alarm temperature
setting

Lower the alarm temperature
setting as follows:
1. Depress the “Set” and “Down”

button for three seconds until
the display reads “HY”

2. Depress the “Set” and “Down”

button for seven seconds until
“PR2” flashes on the display

3. Using the “Down” button, scroll

until the display reads “AL2”

4. Depress the “Set” button and

lower the alarm temperature
setting to your desired setting

This manual is related to the following products: