Standard Protection Mechanisms
The cooling unit is programmed to shut down certain components to protect those
components, as well as the wine inside the cellar, under the following circumstances:
Scenario
What it means
What happens
P1 Alarm
Probe 1, which senses
the temperature inside
the cellar and controls
the on/off cycles of the
cooling unit, has failed
The cooling unit enters a timed
auto-cycle mode until Probe 1 is
repaired or replaced. In this mode,
the cooling unit will turn for 12
minutes and off for 8 minutes.
Optional Protection Mechanisms
CellarPro cooling systems can be programmed to turn off the compressor and
condenser fan in the event of an HA2 alarm, as described below. If you’d like to turn
on this protection mechanism, please call us toll-free at 877.726.8496
P3 > 60°C for more
than 2 hours
The condenser probe
is measuring
temperatures that are
too hot
The compressor and condenser
fan will turn off until the condenser
temperature falls below 60°C
Maintenance
The condenser coils at the back of the cooling unit will collect dust, dirt and lint over
time. It is critically important to clean the coils periodically. If the condenser coils
become clogged, the cooling unit will not have
proper airflow and its performance and longevity
will be compromised.
To clean the coils, simply vacuum or brush the
coils until all dust and lint have been removed. Do
not use compressed air to clean the coils because
it may force dirt particles into the cooling system
and cause serious damage to its internal
components.