Carrier 48TM016-028 User Manual
Page 9
9
Table 1 — Physical Data
LEGEND
*The ZRU140KC compressor is a tandem compressor, consisting of a ZR72KC (25% total
capacity) and a ZR68KC (24% total capacity).
†Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator
coils; and Circuit 2 uses the upper portion of both coils.
**Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to 1
1
/
2
turns open.
††Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to
1
/
2
turns
open.
***Rollout switch is manual reset.
†††A Liquid Propane kit is available as an accessory.
¶The 48TM028 unit requires 2-in. industrial-grade filters capable of handling face velocities up
to 625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 48TM016-028 units have a low-pressure switch (standard) located on the suction
side.
UNIT 48TM
016D/F
020D/F
025D/F
028D/F
NOMINAL CAPACITY (tons)
15
18
20
25
OPERATING WEIGHT
1800
1850
1900
2270
Economizer
90
90
90
90
MoistureMi$er™ Dehumidification Package
40
40
40
40
COMPRESSOR/MANUFACTURER
Scroll, Copeland
Quantity...Model (Ckt 1, Ckt 2)
1...ZR94KC,
1...ZR72KC
1...ZR108KC,
1...ZR94KC
1...ZR125KC,
1...ZR108KC
1...ZRU140KC,*
1...ZR144KC
Capacity Stages (%)
60, 40
55, 45
55, 45
50, 50
Number of Refrigerant Circuits
2
2
2
2
Oil (oz) (Ckt 1, Ckt 2)
85, 60
106, 81
106,106
136, 106
REFRIGERANT TYPE
R-22
Expansion Device
TXV
Operating Charge (lb-oz)
Circuit 1†
19-8
19-8
19-11
26-13
Circuit 2
13-8
19-2
13-14
25-10
CONDENSER COIL
Cross-Hatched
3
/
8
-in. Copper Tubes, Aluminum Lanced,
Aluminum Pre-Coated, or Copper Plate Fins
Rows...Fins/in.
4...15
4...15
4...15
3...15 (2 coils)
Total Face Area (sq ft)
21.7
21.7
21.7
43.4
CONDENSER FAN
Propeller Type
Nominal Cfm
10,500
10,500
14,200
21,000
Quantity...Diameter (in.)
3...22
3...22
2...30
6...22
Motor Hp...Rpm
1
/
2
...1050
1
/
2
...1050
1...1075
1
/
2
...1050
Watts Input (Total)
1100
1100
3400
2200
EVAPORATOR COIL
Cross-Hatched
3
/
8
-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split
Rows...Fins/in.
4...15
4...15
4...15
4...15
Total Face Area (sq ft)
17.5
17.5
17.5
17.5
EVAPORATOR FAN
Centrifugal Type
Quantity...Size (in.)
2...12 x 12
2...12 x 12
2...12 x 12
2...12 x 12
Type Drive
Belt
Belt
Belt
Belt
Nominal Cfm
6000
7200
8000
10,000
Motor Hp
5
5
7.5
10
Motor Nominal Rpm
1745
1745
1745
1740
Maximum Continuous Bhp
6.13
5.90
8.7 [208/230, 575 v]
9.5 [460 v]
10.2 [208/230, 575 v]
11.8 [460 v]
Motor Frame Size
184T
184T
213T
215T
Nominal Rpm High/Low
—
—
—
—
Fan Rpm Range
Low-Medium Static
873-1021
910-1095
1002-1151
1066-1283
High Static
1025-1200
1069-1287
1193-1369
1332-1550
Motor Bearing Type
Ball
Ball
Ball
Ball
Maximum Allowable Rpm
1550
1550
1550
1550
Motor Pulley Pitch Diameter
Low-Medium Static
4.9/5.9
4.9/5.9
5.4/6.6
4.9/5.9
Min/Max (in.)
High Static
4.9/5.9
4.9/5.9
5.4/6.6
4.9/5.9
Nominal Motor Shaft Diameter (in.)
1
1
/
8
1
1
/
8
1
3
/
8
1
3
/
8
Fan Pulley Pitch Diameter (in.)
Low-Medium Static
9.4
9.4
9.4
8.0
High Static
8.0
8.0
7.9
6.4
Nominal Fan Shaft Diameter (in.)
1
7
/
16
1
7
/
16
1
7
/
16
1
7
/
16
Belt, Quantity...Type...Length (in.)
Low-Medium Static
1...BX...50
1...BX...50
1...BX...53
2...BX...50
High Static
1...BX...48
1...BX...48
1...BX...50
2...BX...47
Pulley Center Line Distance (in.)
13.3-14.8
13.3-14.8
14.6-15.4
14.6-15.4
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Low-Medium Static
37
37
37
36
High Static
44
34
44
45
Movable Pulley Maximum Full Turns
From Closed Position
6**
6††
6**
6††
Factory Speed
3.5
3.5
3.5
3.5
Factory Speed Setting (rpm)
Low-Medium Static
965
1002
1120
1182
High Static
1134
1178
1328
1470
Fan Shaft Diameter at Pulley (in.)
1
7
/
16
1
7
/
16
1
7
/
16
1
7
/
16
Bhp
— Brake Horsepower
TXV
— Thermostatic Expansion Valve