Carrier 48TM016-028 User Manual

Page 25

background image

25

Outdoor air leakage is shown in Table 9. Return air pressure

drop is shown in Table 10.

Table 9 — Outdoor Air Damper Leakage

Table 10 — Return Air Pressure Drop (in. wg)

ECONOMI$ERIV STANDARD SENSORS
Outdoor Air Temperature (OAT) Sensor — The outdoor air
temperature sensor (HH57AC074) is a 10 to 20 mA device
used to measure the outdoor-air temperature. The outdoor air
temperature is used to determine when the EconoMi$erIV can
be used for free cooling. The sensor must be field-relocated.
See Fig. 33. The operating range of temperature measurement
is 40 to 100 F.
Supply Air Temperature (SAT) Sensor — The supply air
temperature sensor is a 3 K thermistor located at the inlet of the
indoor fan. See Fig. 34. This sensor is factory installed. The op-
erating range of temperature measurement is 0° to 158 F. See
Table 11 for sensor temperature/resistance values.

The temperature sensor looks like an eyelet terminal with

wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
Low Temperature Compressor Lockout Switch — The Econo-
Mi$erIV is equipped with an ambient temperature lockout
switch located in the outdoor airstream which is used to lockout
the compressors below a 42 F ambient temperature. See Fig. 33.

Table 11 — Supply Air Sensor Temperature/

Resistance Values

DAMPER STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

LEAKAGE (cfm)

35

53

65

75

90

102

CFM

4500

5000

5400

6000

7200

7500

9000 10,000 11,250

0.040 0.050 0.060 0.070 0.090 0.100 0.110

0.120

0.140

TEMPERATURE (F)

RESISTANCE (ohms)

–58

200,250

–40

100,680

–22

53,010

–4

29,091

14

16,590

32

9,795

50

5,970

68

3,747

77

3,000

86

2,416

104

1,597

122

1,080

140

746

158

525

176

376

185

321

194

274

212

203

230

153

248

116

257

102

266

89

284

70

302

55

ECONOMI$ERIV

OUTDOOR AIR
TEMPERATURE SENSOR
(INSTALLED OPERATION
POSITION)

SCREWS

SCREWS

FRAME

TOP

LOW TEMPERATURE
COMPRESSOR
LOCKOUT SWITCH

ACTUATOR

ECONOMI$ERIV

FLANGE
AND SCREWS
(HIDDEN)

CONTROLLER

SUPPLY AIR
TEMPERATURE SENSOR
LOCATION

TR

1

24

Va

c

CO

M

TR

24

Va

c

HO

T

1

2

3

4

5

EF

EF

1

+

_

P1

T1

P

T

N

EX

H

2V

10

V

EX

H

Se

t

Se

t

2V

10

V

2V

10

V

DC

V

DC

V

Fr

ee

Co

ol

B

C

A

D

SO

+

SR

+

SR

SO

AQ

1

AQ

DC

V

Mi

n

Po

s

Op

en

Ma

x

N1

Fig. 33 — EconoMi$erIV Component Locations —

End View

Fig. 34 — EconoMi$erIV Component Locations —

Side View

FRAME
TOP

SCREWS

ECONOMI$ER2

SCREWS

Fig. 35 — EconoMi$er2 Component Locations