Carrier 50HG014-028 User Manual
Page 11

11
Table 2A — Electrical Data (Units Without Optional Convenience Outlet) (cont)
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
See Legend and Notes on page 10.
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1
No. 2
No. 3
Min Max RLA
LRA
RLA
LRA
RLA
LRA
Qty Hp
FLA
(ea)
kW
FLA
Hp
FLA
Qty Hp
FLA
(ea)
MCA
MOCP*
FLA
016
208/230
187
253
16.7
130.0
16.7
130.0
16.7
130.0
4.0
1
/
4
1.5
—
—
3.7
10.6/ 9.6
—
—
—
71/ 70
80/ 80
80/ 80
2
1.0
5.9
83/ 82
90/ 90
100/ 90
5.0
16.7/15.2
—
—
—
77/ 75
90/ 90
90/ 90
2
1.0
5.9
89/ 87
100/100
100/100
19/25
52/ 60
3.7
10.6/ 9.6
—
—
—
78/ 87
80/ 90
80/ 90
2
1.0
5.9
93/102
100/110
100/100
5.0
16.7/15.2
—
—
—
86/ 94
90/100
90/ 90
2
1.0
5.9
101/109
110/110
100/110
38/50
104/120
3.7
10.6/ 9.6
—
—
—
143/132
150/150
150/150
2
1.0
5.9
158/147
175/150
150/175
5.0
16.7/15.2
—
—
—
151/139
175/150
150/175
2
1.0
5.9
166/154
175/175
175/175
56/75†
156/180
3.7
10.6/ 9.6
—
—
—
71/ 70†
80/ 80†
80/ 80†
2
1.0
5.9
83/ 82†
90/ 90†
100/ 90†
5.0
16.7/15.2
—
—
—
77/ 75†
90/ 90†
90/ 90†
2
1.0
5.9
89/ 87†
100/100†
100/100†
460
414
506
9.0
70.0
9.0
70.0
9.0
70.0
4.0
1
/
4
0.7
—
—
3.7
4.8
—
—
—
37
45
40
2
1.0
3.1
43
50
50
5.0
7.6
—
—
—
40
45
45
2
1.0
3.1
46
50
60
25
30
3.7
4.8
—
—
—
44
45
45
2
1.0
3.1
51
60
50
5.0
7.6
—
—
—
47
50
45
2
1.0
3.1
55
60
60
50
60
3.7
4.8
—
—
—
66
80
80
2
1.0
3.1
74
80
90
5.0
7.6
—
—
—
70
80
80
2
1.0
3.1
77
80
90
75
90
3.7
4.8
—
—
—
96
110
110
2
1.0
3.1
104
110
125
5.0
7.6
—
—
—
100
110
125
2
1.0
3.1
107
125
125
575
518
633
7.0
55.0
7.0
55.0
7.0
55.0
4.0
1
/
4
0.7
—
—
3.0
3.9
—
—
—
29
35
35
2
1.0
3.1
36
40
40
5.0
6.1
—
—
—
32
35
35
2
1.0
3.1
38
40
45
25
24
3.0
3.9
—
—
—
35
35
35
2
1.0
3.1
43
45
40
5.0
6.1
—
—
—
38
40
35
2
1.0
3.1
45
50
45
48
46
3.0
3.9
—
—
—
62
70
60
2
1.0
3.1
70
80
70
5.0
6.1
—
—
—
65
70
60
2
1.0
3.1
73
80
70
78
75
3.0
3.9
—
—
—
80
90
100
2
1.0
3.1
88
100
100
5.0
6.1
—
—
—
83
90
100
2
1.0
3.1
90
100
110
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1
No. 2
No. 3
Min
Max
RLA
LRA
RLA
LRA
RLA
LRA
Qty
Hp
FLA
(ea)
kW
FLA
Hp
FLA
Qty
Hp
FLA
(ea)
MCA
MOCP*
FLA
016
208/240
187
253
NA
NA
NA
NA
NA
NA
NA
NA
NA
56/75
156/180
NA
NA
NA
NA
NA
156/180
175/200
200/225
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1
No. 2
No. 3
Min
Max
RLA
LRA
RLA
LRA
RLA
LRA
Qty Hp
FLA
(ea)
kW
FLA
Hp
FLA
Qty
Hp
FLA
(ea)
MCA
MOCP*
FLA
016
208/230
187
253
16.7
130.0
16.7
130.0
16.7
130.0
4.0
1
/
4
1.5
56/75
156/180
3.7
10.6/ 9.6
—
—
—
169/192
200/225
200/225
2
1.0
5.9
184/207
200/225
225/250
5.0
16.7/15.2
—
—
—
177/199
200/225
200/225
2
1.0
5.9
192/214
200/225
225/250