beautypg.com

Carrier 50HG014-028 User Manual

Page 10

background image

10

Table 2A — Electrical Data (Units Without Optional Convenience Outlet)

LEGEND AND NOTES FOR TABLES 2A AND 2B

LEGEND

*Fuse or HACR circuit breaker.
†208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the

branch circuit values for the refrigeration part of the system. The following two tables list
the branch circuit values for the electric heat and values for a feeder circuit for both branch
circuits.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment

(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable
2%.

3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired sepa-

rately in the field.

4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v

units, respectively.

5. The FLA load amps provided in the table for electric heaters are based on 208/240, 480

and 600 v.

6. MCA calculation for 50HG014-028 units with electric heaters over 50 kW is = 1.25 x

(IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA).

UNIT
SIZE

50HG

NOMINAL

VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

ELECTRIC

HEAT

IFM

POWER

EXHAUST

POWER

SUPPLY

DISCONNECT

SIZE

No. 1

No. 2

No. 3

Min

Max

RLA

LRA

RLA

LRA

RLA

LRA

Qty Hp

FLA

(ea)

kW

FLA

Hp

FLA

Qty

Hp

FLA

(ea)

MCA

MOCP*

FLA

014

208/230

187

253

19.2

146.0

19.2

146.0

4.0

1

/

4

1.5

3.7

10.6/ 9.6

60/ 59

70/ 70

70/ 70

2

1.0

5.9

72/ 71

90/ 80

80/ 80

5.0

16.7/15.2

66/ 64

80/ 80

80/ 70

2

1.0

5.9

78/ 76

90/ 90

90/ 90

12/16

33/ 38

3.7

10.6/ 9.6

60/ 60

70/ 70

70/ 70

2

1.0

5.9

72/ 74

90/ 80

80/ 80

5.0

16.7/15.2

66/ 67

80/ 80

80/ 70

2

1.0

5.9

78/ 81

90/ 90

90/ 90

19/25

52/ 60

3.7

10.6 /9.6

78/ 87

80/ 90

80/ 90

2

1.0

5.9

93/102

100/110

90/100

5.0

16.7/15.2

86/ 94

90/100

80/ 90

2

1.0

5.9

101/109

110/110

100/110

38/50

104/120

3.7

10.6/ 9.6

143/132

150/150

150/150

2

1.0

5.9

158/147

175/150

150/175

5.0

16.7/15.2

151/139

175/150

150/175

2

1.0

5.9

166/154

175/175

175/175

460

414

506

9.5

73.0

9.5

73.0

4.0

1

/

4

0.7

3.7

4.8

29

35

35

2

1.0

3.1

35

40

40

5.0

7.6

32

40

35

2

1.0

3.1

38

45

45

15

18

3.7

4.8

29

35

35

2

1.0

3.1

36

40

40

5.0

7.6

32

40

35

2

1.0

3.1

40

45

45

25

30

3.7

4.8

44

45

45

2

1.0

3.1

51

60

50

5.0

7.6

47

50

45

2

1.0

3.1

55

60

60

50

60

3.7

4.8

66

80

80

2

1.0

3.1

74

80

90

5.0

7.6

70

80

80

2

1.0

3.1

77

80

90

575

518

633

7.6

58.4

7.6

58.4

4.0

1

/

4

0.7

3.0

3.9

24

30

30

2

1.0

3.1

30

35

35

5.0

6.1

26

30

30

2

1.0

3.1

32

35

35

16

15

3.0

3.9

24

30

30

2

1.0

3.1

31

35

35

5.0

6.1

26

30

30

2

1.0

3.1

34

35

35

25

24

3.0

3.9

35

35

35

2

1.0

3.1

43

45

40

5.0

6.1

38

40

35

2

1.0

3.1

45

50

45

48

46

3.0

3.9

62

70

60

2

1.0

3.1

70

80

70

5.0

6.1

65

70

60

2

1.0

3.1

73

80

70

FLA

Full Load Amps

MCA

Minimum Circuit Amps

HACR — Heating, Air Conditioning and

MOCP — Maximum Overcurrent Protection

Refrigeration

NEC

National Electrical Code

IFM

Indoor (Evaporator) Fan Motor OFM

Outdoor (Condenser) Fan Motor

LRA

Locked Rotor Amps

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

= 457

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.

7

457