MIB Objects

Table 11. IETF UPS MIB Objects (continued)

Variable Name and Relative XML Object Path

Variable Unit

Variable Type

OID

upsAlarmUpsOffAsRequested

Relative XML Object Path not implementated

1.6.3.12

upsAlarmChargerFailed

UPS.BatterySystem.Charger.PresentStatus.InternalFailure

1.6.3.13

upsAlarmUpsOutputOff

UPS.PowerSummary.PresentStatus.Good

1.6.3.14

upsAlarmUpsSystemOff

Relative XML Object Path not implementated

1.6.3.15

upsAlarmFanFailure

UPS.PowerSummary.PresentStatus.FanFailure

1.6.3.16

upsAlarmFuseFailure

UPS.BatterySystem.Battery.PresentStatus.FuseFault

UPS.PowerConverter.Input[1].PresentStatus.FuseFault

UPS.PowerConverter.Inverter.PresentStatus.FuseFault

1.6.3.17

upsAlarmGeneralFault

UPS.PowerSummary.PresentStatus.InternalFailure

1.6.3.18

upsAlarmDiagnosticTestFailed

Relative XML Object Path not implementated

1.6.3.19

upsAlarmCommunicationsLost

UPS.PowerSummary.PresentStatus.CommunicationLost

1.6.3.20

upsAlarmAwaitingPower

Relative XML Object Path not implementated

1.6.3.21

upsAlarmShutdownPending

UPS.PowerSummary.DelayBeforeShutdown

1.6.3.22

upsAlarmShutdownImminent

UPS.PowerSummary.PresentStatus.ShutdownImminent

1.6.3.23

upsTestResultsSummary

UPS.BatterySystem.Battery.Test

1.7.3

Integer

{1,2,3,4,5,6}

upsShutdownType

No Relative XML Object Path

1.8.1

Integer

Sec

upsShutdownAfterDelay

UPS.PowerSummary.DelayBeforeShutdown

1.8.2

Integer

Sec

upsStartupAfterDelay

UPS.PowerSummary.DelayBeforeStartup

1.8.3

Integer

Sec