Dell UPS 1000R User Manual
Page 61
61
MIB Objects
|
Table 11. IETF UPS MIB Objects (continued)
Variable Name and Relative XML Object Path
Variable Unit
Variable Type
OID
upsBypassNumLines
No Relative XML Object Path
1.5.2
Integer
—
upsBypassVoltage
UPS.PowerConverter.Input[2].Voltage
1.5.3.1.2
Integer
V
upsBypassCurrent
UPS.PowerConverter.Input[2].Current
1.5.3.1.3
Integer
0.1A
upsBypassPower
No Relative XML Object Path
1.5.3.1.4
Integer
W
upsAlarmsPresent
No Relative XML Object Path
1.6.1
Gauge
—
upsAlarmTable
No Relative XML Object Path
—
—
—
upsAlarmBatteryBad
UPS.PowerSummary.PresentStatus.NeedReplacement
1.6.3.1
—
—
upsAlarmOnBattery
UPS.PowerSummary.PresentStatus.Discharging
1.6.3.2
—
—
upsAlarmLowBattery
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit
1.6.3.3
—
—
upsAlarmDepletedBattery
Relative XML Object Path not implementated
1.6.3.4
—
—
upsAlarmTempBad
UPS.PowerSummary.PresentStatus.OverTemperature
1.6.3.5
—
—
upsAlarmInputBad
UPS.PowerConverter.Input[1].PresentStatus.VoltageOutOfRange
1.6.3.6
—
—
upsAlarmOutputBad
Relative XML Object Path not implementated
1.6.3.7
—
—
upsAlarmOutputOverload
UPS.PowerSummary.PresentStatus.Overload
1.6.3.8
—
—
upsAlarmOnBypass
UPS.PowerConverter.Input[2].PresentStatus.Used
1.6.3.9
—
—
upsAlarmBypassBad
UPS.PowerConverter.Input[2].PresentStatus.Good
1.6.3.10
—
—
upsAlarmOutputOffAsRequested
Relative XML Object Path not implementated
1.6.3.11
—
—