beautypg.com

Dell UPS 5600R User Manual

Page 28

background image

28

|

Installation

AC Mains

Wall

2-Pole

Breaker

UPS

Line

Neutral/L2

Figure 17. Circuit Breaker Diagram

To hardwire the UPS input:

1

Switch off utility power at the distribution point where the UPS will be connected. Be absolutely
sure there is no power.

2

Remove the terminal block cover (four screws) and retain.

Figure 18. Removing the Terminal Block Cover

3

Punch a hole in the terminal block cover for the input conduit using a Greenlee

®

punch or similar

device. The hole accommodates 3/4” or 1” IMC conduit.

4

Pull the input wire through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach
a flexible metal fitting to the end of the conduit.