beautypg.com

Hardwiring the ups input – Dell UPS 5600R User Manual

Page 27

background image

27

Installation

|

Continue for each UPS. On the last UPS in the daisy-chain, connect a REPO connector (without a
jumper) in the REPO port labeled “OUT.”

7

Verify that the externally-connected REPO switch is not activated to enable power to the UPS
output receptacles.

8

For hardwired models, continue to the following section, “Hardwiring the UPS Input.” Otherwise,
continue to “UPS Initial Startup” on page 31.

Hardwiring the UPS Input

WARNING:

Only qualified service personnel (such as a licensed electrician) shall perform the electrical

installation. Risk of electrical shock.

The Dell Online Rack hardwired models require a dedicated branch circuit that meets the following
requirements:

S

The protection device requires a two-pole disconnection device between the UPS input and the
mains (see Figure 17)

S

The breaker must be wall-mounted and be readily accessible to the operator

S

For Europe, the breaker must meet the IEC/EN 60934 standard and have a contact air gap of at
least 3 mm

S

200–240 Vac

S

Single-phase

-

5600W/208V model is phase-to-phase (can also be used on a split-phase 120/240 Vac input)

-

5600W/230V model is phase-to-neutral

S

50/60 Hz

S

Flexible metal conduit (recommended for ease of service and maintenance)