beautypg.com

Control operation during regeneration, Control operation during programming, Control operation during a power failure – Culligan Soft-Minder 2005 User Manual

Page 13

background image

6. Set Regeneration Day Override. Use the Set Up or

Set Down buttons to set the maximum number of

days before a Regeneration cycle must occur.

7. Press the Extra Regeneration button to exit the

program.

Immediate Regeneration Valves With Days Between Regeneration Override Set

When the valve reaches its set Days Since Regeneration Override value, a Regeneration cycle initiates immediately. This event

occurs regardless of the Volume Remaining display reaching zero gallons.

Delayed Regeneration Valves With Days Between Regeneration Override Set

When the valve reaches its set Days Since Regeneration Override value a Regeneration cycle initiates at the preset Regeneration

Time . This event occurs regardless of the Volume Remaining display reaching zero gallons.

Control Operation During Regeneration

In Regeneration the control displays a special Regeneration display. While in Regeneration the control shows the current

Regeneration step number to which the valve is advancing or has reached, and the time remaining in that step. The
displayed step number flashes until the valve completes driving

to this Regeneration step position. Once all Regeneration

steps are complete the valve returns to In Service and resumes

normal operation.
Pressing the Extra Cycle button during a Regeneration cycle

immediately advances the valve to the next cycle step position and resumes normal step timing.

Control Operation During Programming

The control only enters the Program Mode with the valve In Service . While in the Program Mode the control continues to operate

normally monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently. There

is no need for battery backup power.

Control Operation During A Power Failure

During a power failure all control displays and programming are stored for use upon power re-application. The control retains these

values for years, if necessary, without loss. The control is inoperative and any calls for Regeneration are delayed. The control,

upon power re-application, resumes normal operation from the point that it was interrupted. An inaccurate or flashing Time of Day

display indicates that a power outage has occurred.

Note: Refer to the 9100 Control Service Manual and the SE Timer Supplemental Service Manual for
additional information on programming and start-up procedures.

Installation

13