Dell UPS 4200R User Manual
Page 73
73
MIB Objects
|
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path
Trap Level
Trap
trapChargerOk
Charger ok
UPS.BatterySystem.Charger.PresentStatus.InternalFailure = 0
38
1
trapEepromFailure
EEPROM failure
UPS.PowerSummary.PresentStatus.ConfigurationFailure = 1
39
3
trapEepromOk
EEPROM ok
UPS.PowerSummary.PresentStatus.ConfigurationFailure = 0
40
1
trapShutdownImminent
Shutdown imminent
UPS.PowerSummary.PresentStatus.ShutdownImminent = 1
41
3
trapShutdownImminentOver
Shutdown imminent over
UPS.PowerSummary.PresentStatus.ShutdownImminent = 0
42
1
trapBatteryLow
Battery low
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit = 1
43
3
trapBatteryOk
Battery ok
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit = 0
44
1
trapOutputShortCircuit
Output short circuit
UPS.PowerConverter.Output.PresentStatus.ShortCircuit = 1
45
3
trapOutputReturnFromShortCircuit
Output return from short circuit
UPS.PowerConverter.Output.PresentStatus.ShortCircuit = 0
46
1
trapUtilityNotPresent
Utility not present
UPS.PowerConverter.Input[1].PresentStatus.VoltageOutOfRange = 1
47
2
trapUtilityPresent
Utility present
UPS.PowerConverter.Input[1].PresentStatus.VoltageOutOfRange = 0
48
1