Century Jefferson User Manual
Page 22

22
22
Jefferson Direct Vent/Natural Vent Gas Heater
30004177
Connect the Gas Supply Line
Check the Rating Plate attached by a steel cable to the 
firebox, to confirm that you have the appropriate firebox 
for the type of fuel to be used. The Jefferson may be 
converted from one gas to another using the appropri-
ate Fuel Conversion Kit listed on Page 34.
In the U.S.; Gas connection should be made in ac-
cordance with current National Fuel Gas Code, ANSI 
Z223.1/NFPA 54. Since some municipalities have 
additional local codes, be sure to consult your local 
authority.
In Canada; consult the local authority and CSA-B149.1
installation code.
Always check for gas leaks with a mild 
soap and water solution. Do not use an 
open flame for leak testing.
Light the pilot according to the directions on Page 26, 
before going to the next step.
This appliance should only be connected 
by a qualified gas technician. Test to 
confirm manifold pressures as specified 
below.
The Jefferson Heater and its individual shutoff 
valve must be disconnected from the gas supply 
piping during any pressure testing of that system 
at test pressures in excess of 1/2 psig (3.5 kPa).
The Jefferson Heater must be isolated from the 
gas supply piping system by closing its indi-
vidual manual shutoff valve during any pressure 
testing of the gas supply piping system at test 
pressure equal to or less than 1/2 psig.
There must be a gas shutoff between the stove 
and the supply.
In order to connect Natural Gas, use a fitting 
with 3/8” NPT on the valve side and 1/2” natural 
gas supply line with an input of 28,000 BTUs at a 
manifold pressure of 3.5” between minimum inlet 
supply of 5.5” w.c. and maximum of 14.0” w.c. 
In order to connect Propane, use a fitting with 3/8” 
NPT on the valve side and 1/2” propane gas sup-
ply line with an input of 28,000 BTUs at a manifold 
pressure of 10.0” between a minimum inlet supply 
of 11.0” w.c. and maximum of 14.0” w.c.
CAUTION
Burner Information
The appliance must only use the gas specified on the 
rating plate, unless converted using a CFM Corporation 
Fuel Conversion Kit. To convert from Natural Gas to LP 
use Kit #30004180.
Conversion instructions are provided with each kit and 
beginning on Page 28 in this manual.
THIS APPLIANCE SHOULD BE CONNECTED
TO THE GAS SUPPLY ONLY BY A QUALI-
FIED GAS SERVICE TECHNICIAN. FOLLOW
ALL LOCAL CODES.
THERE MUST BE A GAS SHUT-OFF BE-
TWEEN THE STOVE AND THE SUPPLY.
In order to connect Natural Gas, use a fitting with 3/8” 
NPT on the valve side and 1/2” natural gas supply line 
with an input of 28,000 BTUs at a manifold pressure 
of 3.5” between minimum inlet supply of 5.5” w.c. and 
maximum of 14.0” w.c. 
In order to connect Propane, use a fitting with 3/8” 
NPT on the valve side and 1/2” propane gas supply line 
with an input of 28,000 BTUs at a manifold pressure of 
10.0” between a minimum inlet supply of 11.0” w.c. and 
maximum of 14.0” w.c.
Air Shutter Adjustment
The Jefferson is shipped from the factory with the air 
shutter adjusted to the minimum allowed opening. Refer 
to Table 1. Based on the altitude where the stove is 
located, a shutter adjustment is acceptable to provide 
mixed balance of flame color/glow. To adjust the shutter 
opening, follow the steps below.
NOTE: The air shutter may only be adjusted to a more 
open position. The factory setting is the minimum al-
lowable air shutter setting.
Table 1. Air Shutter Adjustment
Minimum rear injector air inlet openings
Model
Natural Gas
LP
Direct Vent
1/2” (13 mm)
1/2” (13 mm)
Natural Vent
1/2” (13 mm)
1” (25 mm)
Air Shutter Adjustment Instructions
To adjust the air shutter, follow these steps:
CAUTION: Allow unit to cool if it has been in 
operation.
1. Remove stove front. Lift stove front up and then
swing bottom out and away to disengage from the 
stove body. (Fig. 37)
2. Swing open the swiveling latches at the top left and
right corners of the glass frame. (Page 14, Fig. 12)
