beautypg.com

Jefferson direct vent /natural vent gas heater, Vertical (through the roof) vent assembly – Century Jefferson User Manual

Page 19

background image

19

Jefferson Direct Vent /Natural Vent Gas Heater

30004177

ST218

install snorkel

12/6/99 djt

Wall Screws

and Anchors

Snorkel

Termination

Cap

Waterproof Seal

Around PIpe

Firestop

4” Clearance

Gravel

Drain

Window
Well

ST218

Fig. 28 Snorkel kit installation.

3. Cut the opening:
CFM System: 9³⁄₈” x 9³⁄₈” (240 x 240 mm)
DuraVent System: 10” x 10” (254 x 254 mm)
4. Plumb any additional opening through the roof or

other construction that may be needed. In all cases,
the opening must provide a minimum of 1” (25 mm)
clearance to the vent pipe.

5. Place the stove in its final position.
6. Install firestop(s) #7DVFS and Attic Insulation Shield

#7DVAIS as needed. (Fig. 30) If there is a room
above ceiling level, a firestop must be installed on
both the bottom and top sides of the ceiling joists.
If an attic is above ceiling level, an attic insulation
shield must be installed.

ST219

snorkel detail

12/6/99 djt

Recessed Wall

Sheet Metal

Screws and

Bracket

Wall Screws

and Anchors

Waterproof Seal

Around Pipe

ST219

Fig. 29 Use extension brackets to mount snorkel against
recessed wall.

Firestop

Finishing

Collar

7” Pipe

Wall Plate

ST222

vent thru ceiling

12/99

#7DVAIS

Attic Insulation

Shield

#7DVFS

Firestop in

Upper Floor

#7DVFS

Firestop in

Ceiling

Use Four
8d Nails

ST222

Fig. 30 Install firestops and attic insulation shield.

Vertical (Through the Roof)

Vent Assembly

Note that all vertically terminated installations
must, where specified, use the restrictor plate to
comply with Vertical Termination Window (Page 9,
Figure 8),
included in the hardware bag.
Make certain the vent system conforms to all other
requirements for vertical termination as specified on
Page 9.
This installation will require you to first determine the
roof pitch and use the appropriate vent components.
Refer to Figures 8 and 9 on Pages 9 and 10.
1. Locate the final position of the stove, observing all

clearances for both the vent and the stove.

2. Plumb to the center of the inner (4”) flue collar from

the ceiling above, and mark that location.

7. Install the appropriate roof support and flashing,

making certain that the upper flange of the flashing
base is below the shingles. (Fig. 31)

8. Install appropriate pipe sections until the vent run

reaches above the flashing. The enlarged ends of
the vent sections always face downward.

9. Install the storm collar and seal around the joints.

(Fig. 31)

10. Add additional vent lengths to achieve the proper

overall height.

11. Apply cement to the inner and outer termination col-

lars and install the terminal cap.

Venting System Assembly - Natural Vent

General Information

The Jefferson Heater is shipped from the factory as a
Direct Vent Heater. It may be converted to a Natural
Vent heater by installing the CFM Corporation Model
Z31D00 FSDHAG Draft Hood Adapter.
The Jefferson Heater is approved for installation as a
Natural Vent unit. CFM Direct Vent outer pipe (7FSSK)
could be used directly after the Draft Hood Adapter