Removing the rack doors, Marking the rack, Figure 1-3 – Dell PowerEdge 750 User Manual
Page 11: One rack unit
Rack Installation Guide
1-9
4
Installing the system in the rack
5
Routing cables
6
Replacing the rack doors
NOTE:
Two procedures are provided for task 3. One procedure is for the RapidRails kit,
and one procedure is for the VersaRails kit.
Removing the Rack Doors
See the procedures for removing doors in the documentation provided with your rack cabinet.
CAUTION:
Because of the size and weight of the rack cabinet doors, never attempt to remove or install
them by yourself.
CAUTION:
Store the two doors where they will not injure someone if the doors accidently fall over.
Marking the Rack
For a 1-U system, you must allow 1 U (44 mm, or 1.75 inches) of vertical space for each system you
install in the rack.
Rack cabinets that meet EIA-310 standards have an alternating pattern of three holes per rack unit
with center-to-center hole spacing (beginning at the top hole of a 1-U space) of 15.9 mm, 15.9 mm,
and 12.7 mm (0.625 inch, 0.625 inch, and 0.5 inch) for the front and back vertical rails
(see Figure 1-3). Rack cabinets may have round or square holes.
NOTE:
The vertical rails may be marked by horizontal lines and numbers in 1-U increments. If you want,
you can make a note of the number marking on the rack’s vertical rail. It is not necessary to mark or place
tape on the rack.
Figure 1-3.
One Rack Unit
1 U (44 mm or 1.75 inches)
12.7 mm (0.5 inch)
15.9 mm (0.625 inch)
15.9 mm (0.625 inch)
12.7 mm (0.5 inch)