Manual_GK473_Profibus_EN.doc 15/16

Baumer IVO GmbH & Co. KG

04.05.11

Villingen-Schwenningen,

Germany

Errors in configuration and parameterizing should not occur when the attached GSD file is applied.
Both errors are transferred as single bit by standard diagnostic data and therefore do not require a
specific error code in external data.
In case of configuration error, bit „diag.cfg.fault“ is set in diagnostic byte 1.
In case of parameterizing error, bit „diag.prm_fault is set in diagnostic byte 1.

For any proceedings regarding error status evaluation and treatment please refer to the relevant
Profibus Master documentation.


5.8. Front panel display elements (LEDs)

The gateway’s front panel provides four LEDs to indicate the RS485 and Profibus-DP operating status.

• DP (red) indicates Profibus-DP operating and error status.

- together with green LED: Gateway is awaiting configuration and parameterization

(Profibus status WAIT_PRM)

- sole, red continuous: Profibus alarm

- sole, red flashing quickly (5 Hz): configuration error

- sole, red flashing slowly (1 Hz): parameterization error

• DP (green) indicates Profibus-DP operating status.

- together with red LED: Gateway is awaiting configuration and parameterization

(Profibus -status WAIT_PRM)

- sole, green continuous: active cyclic data transfer with DP-Master

(Profibus status DATA_EXCHANGE)

• TX (yellow) transmission of a token by RS485 interface
• RX (yellow) reception of a token by RS 485 interface