Dynalco Catalyst Monitor User Manual
Page 12
11
”
Calibration”
Select the channel number to configure by pressing the up / down arrows and pressing the
right arrow to select and continue.
The screens allow you to define the “Cal Zero” and “Cal Span” values for any channels that
are configured for 0-1 V, 0-5 V, 0-10 V or 4-20 mA inputs.
Example
A pressure transmitter is connected to channel # 1. The transmitter has a 4-20 mA
output representing a pressure input of 0 - 500 PSI. The “Cal Zero” and “Cal Span”
values would be defined as:
Cal Zero = 0
Cal Span = 500
Note that the “Engineering Units” would be input as PSI in “Channel” configuration
above.
“Alarm Settings”
Select the channel number to configure by pressing the up / down arrows, then pressing the
right arrow to navigate and select the following:
Enable alarms
Yes / No
Alarm Type
Latching / Non-Latching
Alarm Output
None / Output 1 / Output 2 / Output 1 and 2
Alarm Low
threshold for under-trip
Alarm High
threshold for over-trip
Alarm Reset Points
Set Defaults / Set Manually
If “Set Manually” is selected, 2 more screens follow:
Alarm Reset Low
manually set reset hysteresis for low trip
Alarm Reset High
manually set reset hysteresis for high trip
“Alarm Logs”
Selecting the “Alarm Logs” icon will allow you to view any active alarms as well as the history
log for each channel. Select any channel number by pressing the up / down arrows. Then
press the right arrow to view any active or logged alarms. Once an active alarm is
acknowledged, it will be placed into the history log. The history log will continuously store the
last 10 alarms for each channel as well as the time & date of each alarm occurrence.