4 tt4000 display language, 5 tt4000 operating modes, 6 supervisory control interfaces – CAT Titan 250 User Manual
Page 38: 7 system programmability, 8 engineering units

Turbomachinery Package Specification
Titan
250 Generator Set
Minute Log
- data are read and stored at one-minute intervals for the previous 62 days,
one file for each day.
10 Second Log
- data are read at 10-second intervals for the previous 31 days, one file
for each day.
Trigger Log
- data are read at one-second intervals for 6 minutes before a “trigger” event
that is defined in the software. The standard trigger is a shutdown. Six minutes before the
trigger of data are written to a file. Up to 50 trigger logs files can be stored.
9.5.4
TT4000 Display Language
In addition to English, dual language screens are available with English and Spanish
(Latin America), Portuguese (Brazil), French, German or Chinese (simplified). Other
languages can be provided as custom features.
9.5.5
TT4000 Operating Modes
There are two operating modes for the TT4000 software: Design Time and Run Time.
Design Time is used to create or modify a project’s working files. Run Time uses those
files in the normal equipment operation.
9.5.6 Supervisory
Control
Interfaces
The Turbotronic 4 control system can transmit data to, and receive control instructions
from, a supervisory control system. All analog data and the status of all discrete values
are available for transmittal. Interface modules mount in the controller rack and connect
through the rack’s backplane. Available connections are:
• ControlLogix 1.5
• Ethernet
• Data Highway Plus
• Modbus
9.5.7 System
Programmability
The Turbotronic 4 system is fully programmable in the field. Programming requires a
licensed copy of Rockwell Automation’s RSLogix 5000 software installed on a suitable
computer with the corresponding interface card installed. Solar offers two standard
options:
Software, instruction manual, interface card and connecting cable.
Fully configured portable computer with the software, instruction manual, interface card and
connecting cable
9.5.8 Engineering
Units
The following engineering unit options are available for the screen displays:
Metric 1
Metric 2
Metric 3
English
Pressure
kPa bar
kg/cm
3
psig
Temperature
°C °C °C °F
© 2008 Solar Turbines Incorporated. All rights reserved.
TPS250GS/908 - Preliminary