Turbomachinery Package Specification
Titan
250 Generator Set
Table 4.
Start System Specifications
Variable Frequency Drive
Optional Voltage Input Ranges See Note (a)
380 to 460 VAC, (48 to 62 Hz)
500 to 600 VAC, (48 to 62 Hz)
Minimum Input Current
- 380 to 460 VAC Input
525 amps
- 500 to 600 VAC Input
342 amps
Voltage Output Range
0 to 460 VAC, (0 to 240 Hz)
Maximum Line Distribution Capacity
1000 kVa
Maximum Fault Current Capacity See Note (b)
30 000 amps
Maximum Breakaway Amperage
383 amps
Maximum Breakaway Torque
918 N-m (677 ft-lb)
Power Factor
0.96
Efficiency 98%
Minimum/Maximum Operating Temperature
-10 to 40
°C (14 to 104°F)
Heat Rejection
- 380 to 460 VAC Input
7350 watts
- 500 to 600 VAC Input
9485 watts
Input Fuse Rating
600 amp
Approximate Measurements
- Height
220 cm (87 in.)
- Width
69 cm (24 in.)
- Depth
60 cm (28 in.)
Approximate Weight
28 831 kg (850 lb)
- Length
73 cm (29 in.)
- Diameter
46 cm (18 in.)
Starter Motor
Motor Type
Squirrel-cage Induction
Motor Voltage Rating
380 AC, (0 to 133 Hz)
Power
93 kW (125 hp)
Operating Speed
0 to 7000 rpm
Maximum Breakaway Amperage
659 amps
Maximum Breakaway Torque
488 N-m (360 ft-lb)
Minimum/Maximum Operating Temperature
-40 to 60
°C (-40 to 140°F)
Space Heater Voltage
115 VAC, 60 Hz
Approximate Measurements
- Length
66 cm (26 in.)
- Diameter
45.7 cm (18 in.)
Approximate Weight
- AC Starter Motor Assembly
450 kg (990 lb)
Power Wiring
VFD to Starter Motors Power Cable Length
38 m (123 ft), See Note (c)
Turning Gear Motor
Motor Type
Squirrel-cage Induction
Motor Voltage Rating
240 VDC
Power
3.73 kW (5 hp)
Operating Speed
2500 rpm
Turbine Rotation Speed
300 rpm
© 2008 Solar Turbines Incorporated. All rights reserved.
TPS250GS/908 - Preliminary
19