Exide Technologies SCR100 Charger User Manual
Page 24
Instr. 4770-65-95005-00 Page 20
APPENDIX A: SCR100 BATTERY CHARGERS. LIST OF DISPLAY INDICATIONS.
Indication
Abbreviation
Interpretation
1.00
1 hour delay set
Delay before charge starts
2.00
2 hour delay set
Delay before charge starts
3.00
3 hour delay set
Delay before charge starts
4.00
4 hour delay set
Delay before charge starts
5.00
5 hour delay set
Delay before charge starts
6.00
6 hour delay set
Delay before charge starts
8.00
8 hour delay set
Delay before charge starts
CHP
CHamPion
Charger set to sealed Champion
®
batteries
COL
COoL Down
Charger operates at Cool Down Stage
dEL
dELay
Delay set or Charger operates at Delay Stage
End
End
Charge Cycle complete
FAC or F3
Failure of AC power
Failure of mains
FCA
Failure of DC CAble
disconnection
DC cable disconnected from the battery during the
charge
FCC
Or
F2
Failure of Charge Cycle
Battery failed to reach Gassing Voltage (Stage 2)
or
Battery failed to reach End Voltage (Stage 3 of
OPC)
FCd
Failure of Cool down
Battery unplugged during Cool Down Stage
FdC
Failure of dC Fuse
Output DC Fuse Failure
FFF
F… Fatal Failure
Fatal Failure of the charger (Overvoltage or
Overcurrent protection or multifunction of Start /
Stop signal)
FLd
FLooded
Charger set for Flooded batteries
FOC
Failure of Overall
Charge timer
Overall charge cycle timer protection
HI
HIgh Voltage Rejection
Battery connected has voltage more than 2.25VPC
LO
LOw Voltage Rejection
Battery connected has voltage less than 1.70VPC
OFF
OFF
Charger is OFF
OPC
OPportunity Charge
Cycle
Charger set to Opportunity Charge Cycle
rEJ
rEJect
Battery connected has voltage too low or too high
Or
Battery failed to reach 1.70VPC after 5 min of
charge
rFr
reFreshing Stage
Charger operates at Refreshing Stage